Service time: Monday to Friday 9:00-18:00
VAL-US-600D/30/1+0-FM - VAL-US-600D/30/1+0-FM 2910388 PHOENIX CONTACT Type 2 surge protection device
In Stock Hot Product

VAL-US-600D/30/1+0-FM

VAL-US-600D/30/1+0-FM 2910388 PHOENIX CONTACT Type 2 surge protection device

$0.00USD
4149 in stock
Key Specifications
GTIN:4055626445267
Note:Made to Order (non-returnable)
Orderkey:2910388
Packing unit:1 pc
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4055626445267
NoteMade to Order (non-returnable)
Orderkey2910388
Packing unit1 pc
Country of originUS (United States)
Custom tariff number85363030
(Ambient conditions)PBT
(Protective circuit)1 A DC
(UL connection data)EN 61643-11 2012
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions)DIN rail module, two-section, divisible
(Additional descriptions)1056 V AC (120 min / safe failure mode)
Color (Ambient conditions)jet black RAL 9005
SPD Type (Connection data)1
Depth (Key Commercial Data)65.5 mm
Width (Key Commercial Data)17.8 mm
EN type (Ambient conditions)T2
Height (Key Commercial Data)96.8 mm
(Indicator/remote signaling)4.5 Nm (25 mm² ... 35 mm²)
Nom. voltage (Connection data)600 V AC (Single-phase)
Shock (operation) (Dimensions)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Degree of protection (Dimensions)IP20 (only when all terminal points are used)
Screw thread (Protective circuit)M2
Mounting type (Ambient conditions)DIN rail: 35 mm
Vibration (operation) (Dimensions)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Nominal frequency (Connection data)50/60 Hz
Mode of protection (Connection data)L-G
Weight per Piece (excluding packing)137.000 g
Housing material (Ambient conditions)PA 6.6
Operating current (UL specifications)1 A AC
Operating voltage (UL specifications)125 V AC
Stripping length (Protective circuit)7 mm
Tightening torque (UL specifications)2 lbf-in. ... 4 lbf-in.
Connection method (Protective circuit)Plug-in/screw connection via COMBICON
Horizontal pitch (Key Commercial Data)1 Div.
Operating current (Protective circuit)5 mA AC ... 1.5 A AC
Operating voltage (Protective circuit)5 V AC ... 250 V AC
Tightening torque (Protective circuit)0.25 Nm
Mode of protection (Ambient conditions)L-PE
Switching function (Protective circuit)PDT contact
Degree of pollution (Ambient conditions)2
Number of positions (Ambient conditions)1
Screw thread (Indicator/remote signaling)M5
Standards/regulations (UL connection data)IEC 61643-11 2011
Power distribution system (Connection data)Single phase
Ambient temperature (operation) (Dimensions)-40 °C ... 80 °C
IEC power supply system (Ambient conditions)TN-C
IEC test classification (Ambient conditions)II
Nominal voltage UN (Additional descriptions)554/960 V AC (TN-C)
TOV behavior at UT (Additional descriptions)1000 V AC (5 s / withstand mode)
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Stripping length (Indicator/remote signaling)16 mm
Connection method (Indicator/remote signaling)Fork-type cable lug
Nominal discharge current In (Connection data)20 kA
Nominal frequency fN (Additional descriptions)50 Hz (60 Hz)
Tightening torque (Indicator/remote signaling)3 Nm (1,5 mm² ... 16 mm²)
Conductor cross section AWG (UL specifications)30 ... 14
Residual voltage Ures (Additional descriptions)≤ 2.9 kV (at In)
Voltage protection rating VPR (Connection data)2500 V
Conductor cross section AWG (Protective circuit)28 ... 16
Maximum Surge Current per Phase (Connection data)30 kA
Tightening torque (UL indicator/remote signaling)30 lbf-in.
Conductor cross section solid (Protective circuit)0.14 mm² ... 1.5 mm²
Surge protection fault message (Ambient conditions)Optical, remote indicator contact
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Conductor cross section flexible (Protective circuit)0.14 mm² ... 1.5 mm²
Short-circuit current rating (SCCR) (Connection data)200 kA
Voltage protection level Up (Additional descriptions)≤ 2.9 kV
Standby power consumption PC (Additional descriptions)≤ 400 mVA
Maximum continuous voltage UC (Additional descriptions)750 V AC
Conductor cross section AWG (Indicator/remote signaling)15 ... 2
Conductor cross section solid (Indicator/remote signaling)1.5 mm² ... 35 mm²
Conductor cross section AWG (UL indicator/remote signaling)10 ... 2
Flammability rating according to UL 94 (Ambient conditions)V-0
Maximum continuous operating voltage MCOV (Connection data)750 V AC
Short-circuit current rating ISCCR (Additional descriptions)25 kA
Conductor cross section flexible (Indicator/remote signaling)1.5 mm² ... 16 mm²
Distance between live and grounded parts (Ambient conditions)8 mm
Max. backup fuse with branch wiring (Additional descriptions)125 A (gG)
Nominal discharge current In(8/20) µs (Additional descriptions)15 kA
Maximum discharge current Imax(8/20) µs (Additional descriptions)30 kA

Product Description

1-channel surge protection device with remote indication contact, for 600 V AC delta configurations.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top