| Parameter | Value |
|---|---|
| PV T2 | |
| Note | 2019 |
| Type | Male |
| Depth | 55.3 mm |
| Width | 17.5 mm |
| Height | 52.4 mm |
| EN type | T2 |
| Altitude | ≤ 2000 m (amsl) |
| Product type | Replacement plug |
| Accessibility | Accessible |
| Mounting type | on base element |
| Material group | I |
| Product family | VALVETRAB MS |
| Horizontal pitch | 1 Div. |
| Housing material | PA 6.6-FR |
| Pollution degree | 2 |
| Response time tA | ≤ 25 ns |
| Connection method | pluggable |
| Shock (operation) | 60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Dimensional drawing | |
| Insulating material | PA 6.6-FR |
| Degree of protection | IP20 |
| Overvoltage category | III |
| SPD failure behavior | OCFM (Open-Circuit Failure Mode) |
| CTI value of material | 600 |
| Installation location | Interior |
| Residual voltage Ures | ≤ 1.9 kV (at In) |
| Vibration (operation) | 7.5g (5-500 Hz/2.5 h/XYZ) |
| IEC power supply system | DC |
| IEC test classification | PV T2 |
| Standards/specifications | EN 61643-31 |
| Insulation resistance Riso | > 5 GΩ (at 500 V DC) |
| Open circuit voltage UOCSTC | ≤ 487.5 V DC |
| Voltage protection level Up | ≤ 1.9 kV |
| Standby power consumption PC | ≤ 25 mVA |
| Surge protection fault message | optical |
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Continuous operating current ICPV | < 20 µA |
| Short-circuit current rating ISCPV | 2000 A |
| Flammability rating according to UL 94 | V-0 |
| Nominal discharge current In(8/20) µs | 20 kA |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Maximum continuous operating voltage UCPV | 585 V DC |
| Installation location of the disconnect device | Internal |
Technical specifications and performance data
Installation and operation guide