| Parameter | Value |
|---|---|
| T1 / T2 | |
| Note | 2011 |
| Type | DIN rail module, two-section, divisible |
| Depth | 76.6 mm (incl. DIN rail 7.5 mm) |
| Width | 71.2 mm |
| Height | 89.8 mm |
| EN type | T1 / T2 |
| Altitude | ≤ 2000 m (amsl) |
| Product type | Arrester combination |
| Mounting type | DIN rail: 35 mm |
| Material group | I |
| Product family | VALVETRAB MS |
| Open side panel | No |
| Horizontal pitch | 4 Div. |
| Housing material | PA 6.6 |
| Pollution degree | 2 |
| Stripping length | 10 mm ... 12 mm |
| Connection method | Push-in connection |
| Cross section AWG | (converted acc. to IEC) |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Mode of protection | L-N |
| Nominal voltage UN | 240/415 V AC (TN-S) |
| Dimensional drawing | |
| Direction of action | 3L-N & N-PE |
| Insulating material | PA 6.6/PBT |
| Number of positions | 4 |
| Degree of protection | IP20 (only when all terminal points are used) |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Overvoltage category | III |
| Residual current IPE | ≤ 5 µA |
| CTI value of material | 600 |
| Rated load current IL | 32 A (at 6 mm²) |
| Response time tA(L-N) | ≤ 25 ns |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| IEC power supply system | TT |
| IEC test classification | I / II |
| TOV behavior at UT(L-N) | 415 V AC (5 s / withstand mode) |
| Standards/specifications | IEC 61643-11 |
| TOV behavior at UT(L-PE) | 415 V AC (5 s / withstand mode) |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
| Residual voltage Ures(L-N) | ≤ 1.2 kV (at In) |
| Conductor cross section AWG | 20 ... 8 |
| Residual voltage Ures(L-PE) | ≤ 2 kV (at In) |
| Residual voltage Ures(N-PE) | ≤ 0.6 kV (at In) |
| Standby power consumption PC | ≤ 810 mVA |
| Conductor cross section rigid | 0.5 mm² ... 10 mm² |
| Surge protection fault message | optical |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Voltage protection level Up(L-N) | ≤ 1.2 kV |
| Voltage protection level Up(L-PE) | ≤ 2 kV |
| Voltage protection level Up(N-PE) | ≤ 1.7 kV |
| Short-circuit current rating ISCCR | 25 kA |
| Max. backup fuse with branch wiring | 160 A (gG) |
| Flammability rating according to UL 94 | V-0 |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum discharge current Imax(8/20) µs | 50 kA |
| Follow current interrupt rating Ifi(N-PE) | 100 A |
| Total discharge current Itotal(8/20) µs | 50 kA |
| Max. backup fuse with V-type through wiring | 32 A (gG - 6 mm²) |
| Total discharge current Itotal(10/350) µs | 50 kA |
| Maximum continuous operating voltage UC(L-N) | 335 V AC |
| Nominal discharge current In(8/20) µs (L-N) | 12.5 kA |
| Maximum continuous operating voltage UC(L-PE) | 335 V AC |
| Maximum continuous operating voltage UC(N-PE) | 264 V AC |
| Nominal discharge current In(8/20) µs (L-PE) | 12.5 kA |
| Nominal discharge current In(8/20) µs (N-PE) | 50 kA |
| Impulse discharge current (10/350) µs (L-PE), charge | 6.25 As |
| Impulse discharge current (10/350) µs (N-PE), charge | 25 As |
| Impulse discharge current (10/350) µs (L-N), charge | 6.25 As |
| Impulse discharge current (10/350) µs (L-N), specific energy | 39 kJ/Ω |
| Impulse discharge current (10/350) µs (N-PE), specific energy | 625 kJ/Ω |
| Impulse discharge current (10/350) µs (L-PE), specific energy | 39 kJ/Ω |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.5 mm² ... 6 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.5 mm² ... 10 mm² |
| Impulse discharge current (10/350) µs (L-PE), peak current value Iimp | 12.5 kA |
| Impulse discharge current (10/350) µs (N-PE), peak current value Iimp | 50 kA |
| Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 12.5 kA |
Technical specifications and performance data