Service time: Monday to Friday 9:00-18:00
VAL-MS-T1/T2 335/12.5/3+1-PT - VAL-MS-T1/T2 335/12.5/3+1-PT 1266415 PHOENIX CONTACT Universal plug-in surge protection device / lightning c..
In Stock Hot Product

VAL-MS-T1/T2 335/12.5/3+1-PT

VAL-MS-T1/T2 335/12.5/3+1-PT 1266415 PHOENIX CONTACT Universal plug-in surge protection device / lightning c..

$508.71USD
60 in stock
Key Specifications
:T1 / T2
Note:2011
Type:DIN rail module, two-section, divisible
Depth:76.6 mm (incl. DIN rail 7.5 mm)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
T1 / T2
Note2011
TypeDIN rail module, two-section, divisible
Depth76.6 mm (incl. DIN rail 7.5 mm)
Width71.2 mm
Height89.8 mm
EN typeT1 / T2
Altitude≤ 2000 m (amsl)
Product typeArrester combination
Mounting typeDIN rail: 35 mm
Material groupI
Product familyVALVETRAB MS
Open side panelNo
Horizontal pitch4 Div.
Housing materialPA 6.6
Pollution degree2
Stripping length10 mm ... 12 mm
Connection methodPush-in connection
Cross section AWG(converted acc. to IEC)
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Mode of protectionL-N
Nominal voltage UN240/415 V AC (TN-S)
Dimensional drawing
Direction of action3L-N & N-PE
Insulating materialPA 6.6/PBT
Number of positions4
Degree of protectionIP20 (only when all terminal points are used)
Nominal frequency fN50 Hz (60 Hz)
Overvoltage categoryIII
Residual current IPE≤ 5 µA
CTI value of material600
Rated load current IL32 A (at 6 mm²)
Response time tA(L-N)≤ 25 ns
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Response time tA(L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
IEC power supply systemTT
IEC test classificationI / II
TOV behavior at UT(L-N)415 V AC (5 s / withstand mode)
Standards/specificationsIEC 61643-11
TOV behavior at UT(L-PE)415 V AC (5 s / withstand mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / withstand mode)
Residual voltage Ures(L-N)≤ 1.2 kV (at In)
Conductor cross section AWG20 ... 8
Residual voltage Ures(L-PE)≤ 2 kV (at In)
Residual voltage Ures(N-PE)≤ 0.6 kV (at In)
Standby power consumption PC≤ 810 mVA
Conductor cross section rigid0.5 mm² ... 10 mm²
Surge protection fault messageoptical
Ambient temperature (operation)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 %
Voltage protection level Up(L-N)≤ 1.2 kV
Voltage protection level Up(L-PE)≤ 2 kV
Voltage protection level Up(N-PE)≤ 1.7 kV
Short-circuit current rating ISCCR25 kA
Max. backup fuse with branch wiring160 A (gG)
Flammability rating according to UL 94V-0
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum discharge current Imax(8/20) µs50 kA
Follow current interrupt rating Ifi(N-PE)100 A
Total discharge current Itotal(8/20) µs50 kA
Max. backup fuse with V-type through wiring32 A (gG - 6 mm²)
Total discharge current Itotal(10/350) µs50 kA
Maximum continuous operating voltage UC(L-N)335 V AC
Nominal discharge current In(8/20) µs (L-N)12.5 kA
Maximum continuous operating voltage UC(L-PE)335 V AC
Maximum continuous operating voltage UC(N-PE)264 V AC
Nominal discharge current In(8/20) µs (L-PE)12.5 kA
Nominal discharge current In(8/20) µs (N-PE)50 kA
Impulse discharge current (10/350) µs (L-PE), charge6.25 As
Impulse discharge current (10/350) µs (N-PE), charge25 As
Impulse discharge current (10/350) µs (L-N), charge6.25 As
Impulse discharge current (10/350) µs (L-N), specific energy39 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), specific energy625 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), specific energy39 kJ/Ω
Conductor cross section, flexible, with ferrule, with plastic sleeve0.5 mm² ... 6 mm²
Conductor cross section flexible, with ferrule without plastic sleeve0.5 mm² ... 10 mm²
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp12.5 kA
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp50 kA
Impulse discharge current (10/350) µs (L-N), peak current value Iimp12.5 kA

Product Description

Universal varistor-based plug-in lightning/surge protective device for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), for lightning protection levels III
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top