Key Specifications
GTIN:4055626445052
Note:Made to Order (non-returnable)
Orderkey:2910366
(General):440 V AC (120 min / withstand mode)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4055626445052
NoteMade to Order (non-returnable)
Orderkey2910366
(General)440 V AC (120 min / withstand mode)
Packing unit1 pc
Country of originUS (United States)
(Connection data)L-G
Custom tariff number85363030
(Ambient conditions)PBT
(Protective circuit)1 A DC
(UL connection data)EN 61643-11 2012
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions)DIN rail module, two-section, divisible
Color (Ambient conditions)jet black RAL 9005
Response time tA (General)≤ 25 ns
SPD Type (Connection data)1
Depth (Key Commercial Data)65.5 mm
Width (Key Commercial Data)53.4 mm
EN type (Ambient conditions)T2
Height (Key Commercial Data)98.7 mm
Nominal voltage UN (General)240/415 V AC (TN-C)
TOV behavior at UT (General)415 V AC (5 s / withstand mode)
(Indicator/remote signaling)4.5 Nm (25 mm² ... 35 mm²)
Nom. voltage (Connection data)240/415 V AC (3-phase Wye)
Nominal frequency fN (General)50 Hz (60 Hz)
Shock (operation) (Dimensions)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Residual voltage Ures (General)≤ 2 kV (at In)
Degree of protection (Dimensions)IP20 (only when all terminal points are used)
Screw thread (Protective circuit)M2
Mounting type (Ambient conditions)DIN rail: 35 mm
Vibration (operation) (Dimensions)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Nominal frequency (Connection data)50/60 Hz
Mode of protection (Connection data)L-L
Weight per Piece (excluding packing)324.000 g
Housing material (Ambient conditions)PA 6.6
Operating current (UL specifications)1 A AC
Operating voltage (UL specifications)125 V AC
Stripping length (Protective circuit)7 mm
Tightening torque (UL specifications)2 lbf-in. ... 4 lbf-in.
Voltage protection level Up (General)≤ 2 kV
Connection method (Protective circuit)Plug-in/screw connection via COMBICON
Horizontal pitch (Key Commercial Data)3 Div.
Operating current (Protective circuit)5 mA AC ... 750 mA AC
Operating voltage (Protective circuit)5 V AC ... 250 V AC
Residual voltage Ures(L-PEN) (General)≤ 1.8 kV (at In)
Tightening torque (Protective circuit)0.25 Nm
Maximum continuous voltage UC (General)385 V AC
Mode of protection (Ambient conditions)L-PEN
Switching function (Protective circuit)PDT contact
Degree of pollution (Ambient conditions)2
Number of positions (Ambient conditions)3
Screw thread (Indicator/remote signaling)M5
Standards/regulations (UL connection data)IEC 61643-11 2011
Power distribution system (Connection data)Wye
Ambient temperature (operation) (Dimensions)-40 °C ... 80 °C
IEC power supply system (Ambient conditions)TN-C
IEC test classification (Ambient conditions)II
Short-circuit current rating ISCCR (General)25 kA
Max. backup fuse with branch wiring (General)125 A (gG)
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Stripping length (Indicator/remote signaling)16 mm
Connection method (Indicator/remote signaling)Fork-type cable lug
Nominal discharge current In (Connection data)20 kA
Tightening torque (Indicator/remote signaling)3 Nm (1,5 mm² ... 16 mm²)
Conductor cross section AWG (UL specifications)30 ... 14
Conductor cross section AWG (Protective circuit)28 ... 16
Nominal discharge current In(8/20) µs (General)20 kA
Maximum Surge Current per Phase (Connection data)40 kA
Tightening torque (UL indicator/remote signaling)30 lbf-in.
Conductor cross section solid (Protective circuit)0.14 mm² ... 1.5 mm²
Maximum discharge current Imax(8/20) µs (General)40 kA
Surge protection fault message (Ambient conditions)Optical, remote indicator contact
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Conductor cross section flexible (Protective circuit)0.14 mm² ... 1.5 mm²
Short-circuit current rating (SCCR) (Connection data)200 kA
Voltage protection rating VPR (L-G) (Connection data)1500 V
Voltage protection rating VPR (L-L) (Connection data)2500 V
Voltage protection rating VPR (L-N) (Connection data)3000 V (240/480S)
Voltage protection rating VPR (N-G) (Connection data)1500 V (240/480S)
Conductor cross section AWG (Indicator/remote signaling)15 ... 2
Conductor cross section solid (Indicator/remote signaling)1.5 mm² ... 35 mm²
Conductor cross section AWG (UL indicator/remote signaling)10 ... 2
Flammability rating according to UL 94 (Ambient conditions)V-0
Conductor cross section flexible (Indicator/remote signaling)1.5 mm² ... 16 mm²
Maximum continuous operating voltage MCOV (L-G) (Connection data)385 V AC
Maximum continuous operating voltage MCOV (L-L) (Connection data)750 V AC
Maximum continuous operating voltage MCOV (L-N) (Connection data)750 V (240/480S)
Maximum continuous operating voltage MCOV (N-G) (Connection data)385 V (240/480S)

Product Description

3-channel surge protection device with remote indication contact for 240/480 V (split phase configuration) or 240/415 V (star connection), 4-wire alternating current.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified