Service time: Monday to Friday 9:00-18:00
VAL-US-240/40/2+0-FM - VAL-US-240/40/2+0-FM 2910364 PHOENIX CONTACT Type 2 surge protection device
In Stock Hot Product

VAL-US-240/40/2+0-FM

VAL-US-240/40/2+0-FM 2910364 PHOENIX CONTACT Type 2 surge protection device

$0.00USD
4412 in stock
Key Specifications
:T2
Note:2011
Type:DIN rail module, two-section, divisible
Color:black (RAL 9005)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
T2
Note2011
TypeDIN rail module, two-section, divisible
Colorblack (RAL 9005)
Depth65.7 mm (incl. DIN rail 7.5 mm)
Width35.6 mm
Height96.8 mm
EN typeT2
UL typetype 1
Altitude≤ 2000 m (amsl)
SPD Type1
Product typeSurge protection for NEMA power supply units
Screw threadM5
Mounting typeDIN rail: 35 mm
Material groupI
Product familyVALVETRAB US
Connection nameRemote fault indicator contact
Nominal voltage240/480 V AC (Split phase)
Article revision04
Horizontal pitch2 Div.
Housing materialPA 6.6
Pollution degree2
Response time tA≤ 25 ns
Stripping length16 mm
Connection methodScrew connection
Nominal frequency50/60 Hz
Operating current5 mA AC ... 750 mA AC
Operating voltage5 V AC ... 250 V AC
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Tightening torque3 Nm (1.5 mm² ... 16 mm²)
Mode of protectionL-PEN
Nominal voltage UN240/480 V AC (TN-C)
Switching functionChangeover contact
TOV behavior at UT415 V AC (5 s / withstand mode)
Dimensional drawing
Direction of action2L-GND
Insulating materialPA 6.6/PBT
Number of positions2
AC operating current1 A AC
Degree of protectionIP20 (only when all terminal points are used)
Nominal frequency fN50 Hz (60 Hz)
Overvoltage categoryIII
CTI value of material600
Residual voltage Ures≤ 1.8 kV (at In)
Standards/regulationsEN 60664-1 / EN 61643-11
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
IEC power supply systemTN-C
IEC test classificationII
Standards/specificationsIEC 61643-11
Power distribution systemSplit phase
Conductor cross section AWG15 ... 2
Voltage protection level Up≤ 1.8 kV
Nominal discharge current In20 kA
Residual voltage Ures(L-PEN)≤ 1.8 kV (at In)
Conductor cross section rigid1.5 mm² ... 35 mm²
Maximum continuous voltage UC385 V AC
Surge protection fault messageOptical, remote indicator contact
Ambient temperature (operation)-40 °C ... 80 °C
Maximum Surge Current per Phase40 kA
Conductor cross section flexible1.5 mm² ... 25 mm²
Permissible humidity (operation)5 % ... 95 %
Short-circuit current rating ISCCR25 kA
Max. backup fuse with branch wiring125 A (gG)
Short-circuit current rating (SCCR)200 kA
Voltage protection rating VPR (L-G)1500 V
Voltage protection rating VPR (L-L)2500 V
Flammability rating according to UL 94V-0
Nominal discharge current In(8/20) µs20 kA
Ambient temperature (storage/transport)-40 °C ... 80 °C
Maximum discharge current Imax(8/20) µs40 kA
Maximum continuous operating voltage MCOV (L-G)385 V AC
Maximum continuous operating voltage MCOV (L-L)750 V AC

Product Description

2-channel surge protection device with remote indication contact, for 240/480 V AC (split phase configuration), 3 wires.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top