Service time: Monday to Friday 9:00-18:00
VAL-SEC-T2-4+0-440-FM - VAL-SEC-T2-4+0-440-FM 1076468 PHOENIX CONTACT Plug-in surge arrester, in accordance with Type 2/Class II, fo..
In Stock Hot Product

VAL-SEC-T2-4+0-440-FM

VAL-SEC-T2-4+0-440-FM 1076468 PHOENIX CONTACT Plug-in surge arrester, in accordance with Type 2/Class II, fo..

$0.00USD
3358 in stock
Key Specifications
:T2
Note:Usable in all low-voltage systems between L-N or L-PEN.Only usable in IT Systems between L-PE and N-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a)
Type:DIN rail module, two-section, divisible
Depth:74.5 mm (incl. DIN rail 7.5 mm)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
T2
NoteUsable in all low-voltage systems between L-N or L-PEN.Only usable in IT Systems between L-PE and N-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a)
TypeDIN rail module, two-section, divisible
Depth74.5 mm (incl. DIN rail 7.5 mm)
Width49.2 mm
Height97.9 mm
EN typeT2
Altitude≤ 2000 m (amsl)
Product typeSurge arrester
Screw threadM5
Mounting typeDIN rail: 35 mm
Material groupI
Product familySEC Family
Connection nameRemote fault indicator contact
Article revision02
Horizontal pitch2.7 Div.
Housing materialPA 6.6-FR 20 % GF
Pollution degree2
Response time tA≤ 25 ns
Stripping length16 mm
Connection methodScrew connection
Operating current5 mA AC ... 1 A AC
Operating voltage5 V AC ... 250 V AC
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Tightening torque4.5 Nm
Mode of protectionL-N
Nominal voltage UN400/690 V AC (TN-S)
Switching functionChangeover contact
TOV behavior at UT581 V AC (5 s / withstand mode)
Dimensional drawing
Direction of action3L-N/PE
Insulating materialPA6.6-FR 20% GF
Number of positions3
Color (Base element)gray (RAL 7042)
Degree of protectionIP20
Nominal frequency fN50 Hz (60 Hz)
Overvoltage categoryIII
CTI value of material600
Rated load current IL40 A (Biconnect M4 fork-type cable lug 6​ mm²)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Color (Male connector)light gray (RAL 7035)
IEC power supply systemTN-S
IEC test classificationII
Standards/specificationsIEC 61643-11
Residual voltage Ures(L-N)≤ 4 kV (at In)
Conductor cross section AWG12 ... 4
Residual voltage Ures(L-PE)≤ 1.9 kV (at In)
Residual voltage Ures(N-PE)≤ 1.9 kV (at In)
Standby power consumption PC≤ 720 mVA
Conductor cross section rigid2.5 mm² ... 25 mm²
Maximum continuous voltage UC440 V AC
Surge protection fault messageOptical, remote indicator contact
Ambient temperature (operation)-40 °C ... 80 °C
Conductor cross section flexible2.5 mm² ... 16 mm²
Permissible humidity (operation)5 % ... 95 %
Voltage protection level Up(L-N)≤ 4 kV
Voltage protection level Up(L-PE)≤ 1.9 kV
Voltage protection level Up(N-PE)≤ 1.9 kV
Short-circuit current rating ISCCR25 kA (for a backup fuse of up to 315 A gG)
Max. backup fuse with branch wiring315 A (gG)
Flammability rating according to UL 94V-0
Nominal discharge current In(8/20) µs20 kA
Ambient temperature (storage/transport)-40 °C ... 80 °C
Maximum discharge current Imax(8/20) µs40 kA
Max. backup fuse with V-type through wiring40 A (gG / Biconnect M4 fork-type cable lug, 6​ mm²)

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top