Service time: Monday to Friday 9:00-18:00
VAL-SEC-T2-3S-350VF-FM - VAL-SEC-T2-3S-350VF-FM 2909590 PHOENIX CONTACT Type 2 surge arrester
In Stock Hot Product

VAL-SEC-T2-3S-350VF-FM

VAL-SEC-T2-3S-350VF-FM 2909590 PHOENIX CONTACT Type 2 surge arrester

$0.00USD
4101 in stock
Key Specifications
(General):63 A (gG / TWIN ferrule 2x 10mm²)
ETIM 5.0 (eCl@ss):EC000941
ETIM 6.0 (eCl@ss):EC000941
(Connection data):EN 61643-11 2012
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
(General)63 A (gG / TWIN ferrule 2x 10mm²)
ETIM 5.0 (eCl@ss)EC000941
ETIM 6.0 (eCl@ss)EC000941
(Connection data)EN 61643-11 2012
UNSPSC 13.2 (ETIM)39121620
(Ambient conditions)PBT-FR
(Protective circuit)1 A DC (30 V DC)
GTIN (Your advantages)4055626371597
Note (Your advantages)Made to Order (non-returnable)
Type (Ambient conditions)DIN rail module, two-section, divisible
Color (Ambient conditions)light grey RAL 7035
Orderkey (Your advantages)2909590
Response time tA (General)≤ 100 ns
EN type (Ambient conditions)T2
Nominal voltage UN (General)240/415 V AC (TN-S)
Altitude (Key Commercial Data)≤ 2000 m (amsl (above mean sea level))
Catalog page (Your advantages)Page 46 (C-4-2017)
Nominal frequency fN (General)50 Hz (60 Hz)
Packing unit (Your advantages)1 pc
Residual current IPE (General)≤ 1 µA
Rated load current IL (General)40 A (Biconnect M4 fork-type cable lug 6​ mm²)
Screw thread (Protective circuit)M2
TOV behavior at UT(L-N) (General)457 V AC (5 s / withstand mode)
Mounting type (Ambient conditions)DIN rail: 35 mm
TOV behavior at UT(N-PE) (General)1200 V AC (200 ms / withstand mode)
Country of origin (Your advantages)DE (Germany)
Residual voltage Ures(L-N) (General)≤ 1.35 kV (at In)
Housing material (Ambient conditions)PA 6.6-FR 20% GF
Residual voltage Ures(L-PE) (General)≤ 1.75 kV (at In)
Residual voltage Ures(N-PE) (General)≤ 0.5 kV (at In)
Stripping length (Protective circuit)7 mm
Connection method (Protective circuit)Plug-in/screw connection via COMBICON
Custom tariff number (Your advantages)85363030
Operating current (Protective circuit)5 mA AC ... 1 A AC
Operating voltage (Protective circuit)5 V AC ... 250 V AC
Tightening torque (Protective circuit)0.25 Nm
eCl@ss 5.1 (Standards and Regulations)27130801
eCl@ss 6.0 (Standards and Regulations)27130805
eCl@ss 8.0 (Standards and Regulations)27130805
eCl@ss 9.0 (Standards and Regulations)27130805
Mode of protection (Ambient conditions)L-N
Standards/regulations (Connection data)IEC 61643-11 2011
Switching function (Protective circuit)PDT contact
Degree of pollution (Ambient conditions)2
Number of positions (Ambient conditions)4
Screw thread (Indicator/remote signaling)M5
Degree of protection (Key Commercial Data)IP20
Voltage protection level Up(L-N) (General)≤ 1.5 kV
Voltage protection level Up(L-PE) (General)≤ 2.3 kV
Voltage protection level Up(N-PE) (General)≤ 1.5 kV
IEC power supply system (Ambient conditions)TN-S
IEC test classification (Ambient conditions)II
Short-circuit current rating ISCCR (General)50 kA
Max. backup fuse with branch wiring (General)200 A (gG)
Maximum continuous voltage UC(N-PE) (General)264 V AC
Stripping length (Indicator/remote signaling)16 mm
Connection method (Indicator/remote signaling)Fork-type cable lug
Tightening torque (Indicator/remote signaling)4.5 Nm
Conductor cross section AWG (Protective circuit)28 ... 16
Conductor cross section solid (Protective circuit)0.14 mm² ... 1.5 mm²
Follow current interrupt rating Ifi(N-PE) (General)100 A (264 V AC)
Surge protection fault message (Ambient conditions)Optical, remote indicator contact
Ambient temperature (operation) (Key Commercial Data)-40 °C ... 80 °C
Conductor cross section flexible (Protective circuit)0.14 mm² ... 1.5 mm²
Max. backup fuse with V-type through wiring (General)40 A (gG / Biconnect M4 fork-type cable lug, 6​ mm²)
Maximum continuous operating voltage UC(L-N) (General)350 V AC
Nominal discharge current In(8/20) µs (L-N) (General)10 kA
Permissible humidity (operation) (Key Commercial Data)5 % ... 95 %
Weight per Piece (excluding packing) (Your advantages)385.000 g
Maximum continuous operating voltage UC(L-PE) (General)350 V AC
Nominal discharge current In(8/20) µs (L-PE) (General)10 kA
Nominal discharge current In(8/20) µs (N-PE) (General)20 kA
Conductor cross section AWG (Indicator/remote signaling)12 ... 4
Maximum discharge current Imax(8/20) µs (L-N) (General)20 kA
Maximum discharge current Imax(8/20) µs (L-PE) (General)20 kA
Maximum discharge current Imax(8/20) µs (N-PE) (General)40 kA
Conductor cross section solid (Indicator/remote signaling)2.5 mm² ... 25 mm²
Flammability rating according to UL 94 (Ambient conditions)V-0
Ambient temperature (storage/transport) (Key Commercial Data)-40 °C ... 80 °C
Conductor cross section flexible (Indicator/remote signaling)1.5 mm² ... 6 mm²

Product Description

Plug-in surge protection device with leakage current proof, according to type 2/class II, for three-phase power supply networks with N and PE separated (5-conductor system: L1, L2, L3, N, PE), with re
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Technical Details

Pluggable surge protective device free of leakage current, in accordance with Type 2/Class II, for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), with remote indication contact.

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top