| Parameter | Value |
|---|---|
| GTIN | 4055626245058 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2907880 |
| (General) | 10 A (gG / B at ISCCR> 100 A) |
| Catalog page | Page 51 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | (DC-) - G |
| (UL specifications) | EN 61643-11 2012 |
| Custom tariff number | 85363030 |
| (Ambient conditions) | PBT-FR |
| Altitude (Dimensions) | ≤ 6000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | light grey RAL 7035 |
| Response time tA (General) | ≤ 25 ns |
| SPD Type (Connection data) | 4CA |
| Depth (Key Commercial Data) | 59.4 mm |
| Width (Key Commercial Data) | 11.7 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| EN type (Ambient conditions) | T2 |
| Height (Key Commercial Data) | 46.4 mm |
| Nominal voltage UN (General) | 350 V DC ... 400 V DC |
| TOV behavior at UT (General) | 551 V DC (5 s / withstand mode) |
| Residual current IPE (General) | ≤ 350 µA DC |
| Shock (operation) (Dimensions) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Residual voltage Ures (General) | ≤ 1.5 kV (at In) |
| Degree of protection (Dimensions) | IP20 |
| Nominal voltage (Connection data) | 400 V DC |
| Mounting type (Ambient conditions) | on base element |
| Vibration (operation) (Dimensions) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| Mode of protection (Connection data) | (DC+) - G |
| Weight per Piece (excluding packing) | 61.600 g |
| Housing material (Ambient conditions) | PA 6.6-FR 20% GF |
| Voltage protection level Up (General) | ≤ 1.5 kV |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Protective circuit) | pluggable |
| Horizontal pitch (Key Commercial Data) | 0.6 Div. |
| Maximum continuous voltage UC (General) | 450 V DC |
| Mode of protection (Ambient conditions) | (DC+) - (DC-) |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 1 |
| Standards/regulations (UL specifications) | IEC 61643-11 2011 |
| Power distribution system (Connection data) | DC |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | DC |
| IEC test classification (Ambient conditions) | II |
| Short-circuit current rating ISCCR (General) | 0.1 kA (without backup fuse) |
| Max. backup fuse with branch wiring (General) | 20 A (gG / B at ISCCR> 200 A) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Nominal discharge current In (Connection data) | 20 kA |
| Measured limiting voltage MLV (Connection data) | 1640 V |
| Nominal discharge current In(8/20) µs (General) | 20 kA |
| Maximum discharge current Imax(8/20) µs (General) | 40 kA |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Max. backup fuse with V-type through wiring (General) | 20 A (gG / B at ISCCR> 200 A) |
| Impulse discharge current (10/350) µs, charge (General) | 0.5 As |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Maximum continuous operating voltage MCOV (Connection data) | 450 V DC |
| Impulse discharge current (10/350) µs, peak value limp (General) | 1 kA |
| Impulse discharge current (10/350) µs, specific energy (General) | 0.25 kJ/Ω |
Technical specifications and performance data