| Parameter | Value |
|---|---|
| GTIN | 4046356948197 |
| Orderkey | 2905346 |
| (General) | 457 V AC (120 min / safe failure mode) |
| Catalog page | Page 42 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (UL specifications) | EN 61643-11 2012 |
| Custom tariff number | 85369010 |
| (Ambient conditions) | PBT-FR |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | light grey RAL 7035 |
| Response time tA (General) | ≤ 25 ns |
| SPD Type (Connection data) | 1CA |
| Depth (Key Commercial Data) | 59.4 mm |
| Width (Key Commercial Data) | 11.7 mm |
| EN type (Ambient conditions) | T2 |
| Height (Key Commercial Data) | 46.4 mm |
| Nominal voltage UN (General) | 240 V AC (TN) |
| TOV behavior at UT (General) | 415 V AC (5 s / withstand mode) |
| Nom. voltage (Connection data) | 277 V AC |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Shock (operation) (Dimensions) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Residual voltage Ures (General) | ≤ 1.5 kV (at In) |
| Degree of protection (Dimensions) | IP20 |
| Mounting type (Ambient conditions) | on base element |
| Vibration (operation) (Dimensions) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| Nominal frequency (Connection data) | 50/60 Hz |
| Mode of protection (Connection data) | L-N |
| Weight per Piece (excluding packing) | 58.700 g |
| Housing material (Ambient conditions) | PA 6.6-FR 20% GF |
| Voltage protection level Up (General) | ≤ 1.5 kV |
| Connection method (Protective circuit) | pluggable |
| Horizontal pitch (Key Commercial Data) | 0.6 Div. |
| Maximum continuous voltage UC (General) | 350 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 1 |
| Standards/regulations (UL specifications) | IEC 61643-11 2011 |
| Power distribution system (Connection data) | Single phase |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TN |
| IEC test classification (Ambient conditions) | II |
| Short-circuit current rating ISCCR (General) | 25 kA (in case of 315 A gG backup fuse) |
| Max. backup fuse with branch wiring (General) | 315 A (gG) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Nominal discharge current In (Connection data) | 20 kA |
| Voltage protection rating VPR (Connection data) | 1200 V |
| Nominal discharge current In(8/20) µs (General) | 20 kA |
| Maximum discharge current Imax(8/20) µs (General) | 40 kA |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Short-circuit current rating (SCCR) (Connection data) | 50 kA |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Maximum continuous operating voltage MCOV (Connection data) | 350 V AC |
Technical specifications and performance data