Service time: Monday to Friday 9:00-18:00
VAL-SEC-T2-2+0-120DC-FM - VAL-SEC-T2-2+0-120DC-FM 2907874 PHOENIX CONTACT Type 2 surge arrester
In Stock Hot Product

VAL-SEC-T2-2+0-120DC-FM

VAL-SEC-T2-2+0-120DC-FM 2907874 PHOENIX CONTACT Type 2 surge arrester

$0.00USD
4094 in stock
Key Specifications
GTIN:4055626244594
Orderkey:2907874
(General):6 kA (for 20 A gG/B backup fuse)
Catalog page:Page 50 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4055626244594
Orderkey2907874
(General)6 kA (for 20 A gG/B backup fuse)
Catalog pagePage 50 (C-4-2017)
Packing unit1 pc
Country of originDE (Germany)
(Connection data)(DC-) - G
Custom tariff number85363010
(Ambient conditions)PBT-FR
(UL connection data)EN 61643-11 2012
Altitude (Dimensions)≤ 6000 m (amsl (above mean sea level))
Type (Ambient conditions)DIN rail module, two-section, divisible
Color (Ambient conditions)light grey RAL 7035
Response time tA (General)≤ 25 ns
SPD Type (Connection data)1
Depth (Key Commercial Data)74.5 mm (incl. DIN rail 7.5 mm)
Width (Key Commercial Data)25.4 mm
(Additional technical data)1 A DC (30 V DC)
(Standards and Regulations)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
EN type (Ambient conditions)T2
Height (Key Commercial Data)97.9 mm
Nominal voltage UN (General)100 V DC ... 120 V DC
TOV behavior at UT (General)174 V DC (5 s / withstand mode)
Residual current IPE (General)≤ 10 µA DC
Shock (operation) (Dimensions)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Rated load current IL (General)40 A (Biconnect M4 fork-type cable lug 6​ mm²)
Degree of protection (Dimensions)IP20
Nominal voltage (Connection data)120 V DC
Mounting type (Ambient conditions)DIN rail: 35 mm
Vibration (operation) (Dimensions)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Mode of protection (Connection data)(DC+) - (DC-)
Weight per Piece (excluding packing)209.600 g
Housing material (Ambient conditions)PA 6.6-FR 20% GF
Operating current (UL specifications)1 A AC
Operating voltage (UL specifications)125 V AC
Tightening torque (UL specifications)4 lbf-in.
China RoHS (Standards and Regulations)Environmentally Friendly Use Period = 50
Horizontal pitch (Key Commercial Data)1.4 Div.
REACh SVHC (Standards and Regulations)Lead 7439-92-1
Maximum continuous voltage UC (General)150 V DC
Mode of protection (Ambient conditions)(DC+) - (DC-)
Degree of pollution (Ambient conditions)2
Number of positions (Ambient conditions)2
Screw thread (Additional technical data)M2
Screw thread (Indicator/remote signaling)M5
Standards/regulations (UL connection data)IEC 61643-11 2011
Power distribution system (Connection data)DC
Ambient temperature (operation) (Dimensions)-40 °C ... 80 °C
IEC power supply system (Ambient conditions)DC
IEC test classification (Ambient conditions)II
Short-circuit current rating ISCCR (General)0.2 kA (without backup fuse)
Stripping length (Additional technical data)7 mm
Connection method (Additional technical data)Plug-in/screw connection via COMBICON
Max. backup fuse with branch wiring (General)20 A (gG / B at ISCCR> 200 A)
Operating current (Additional technical data)5 mA AC ... 1 A AC
Operating voltage (Additional technical data)5 V AC ... 250 V AC (Altitude ≤ 2000 m amsl)
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Stripping length (Indicator/remote signaling)16 mm
Tightening torque (Additional technical data)0.25 Nm
Connection method (Indicator/remote signaling)Fork-type cable lug
Nominal discharge current In (Connection data)20 kA
Switching function (Additional technical data)PDT contact
Tightening torque (Indicator/remote signaling)4.5 Nm
Conductor cross section AWG (UL specifications)30 ... 14
Nominal discharge current In(8/20) µs (General)20 kA
Tightening torque (UL indicator/remote signaling)30 lbf-in.
Maximum continuous voltage UC (Protective circuit)135 V AC (for operation in safety lighting systems)
Maximum discharge current Imax(8/20) µs (General)40 kA
Total discharge current Itotal(8/20) µs (General)40 kA
Voltage protection level Up(DC+) - (DC-) (General)≤ 1.8 kV
Surge protection fault message (Ambient conditions)Optical, remote indicator contact
Voltage protection level Up(DC+/DC-) - PE (General)≤ 0.85 kV
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Max. backup fuse with V-type through wiring (General)20 A (gG / B at ISCCR> 200 A)
Short-circuit current rating (SCCR) (Connection data)50 kA
Conductor cross section AWG (Additional technical data)28 ... 16
Conductor cross section AWG (Indicator/remote signaling)12 ... 4
Impulse discharge current (10/350) µs, charge (General)0.5 As
Conductor cross section solid (Additional technical data)0.14 mm² ... 1.5 mm²
Voltage protection rating VPR (DC+) - G (Connection data)700 V
Voltage protection rating VPR (DC-) - G (Connection data)700 V
Conductor cross section solid (Indicator/remote signaling)2.5 mm² ... 25 mm²
Conductor cross section AWG (UL indicator/remote signaling)10 ... 2
Flammability rating according to UL 94 (Ambient conditions)V-0
Conductor cross section flexible (Additional technical data)0.14 mm² ... 1.5 mm²
Conductor cross section flexible (Indicator/remote signaling)1.5 mm² ... 6 mm²
Voltage protection rating VPR (DC+) - (DC-) (Connection data)1500 V
Impulse discharge current (10/350) µs, peak value limp (General)1 kA
Impulse discharge current (10/350) µs, specific energy (General)0.25 kJ/Ω

Product Description

Plug-in surge protection device, according to Type 2/Class II, for DC current sources with linear service characteristic, with remote indication contact.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top