| Parameter | Value |
|---|---|
| T2 | |
| Note | 2011 |
| Type | Male |
| Color | light gray (RAL 7035) |
| Depth | 59.4 mm |
| Width | 11.7 mm |
| Height | 46.4 mm |
| EN type | T2 |
| Altitude | ≤ 2000 m (amsl) |
| SPD Type | 4CA |
| Product type | Replacement plug |
| Mounting type | on base element |
| Material group | I |
| Product family | SEC Family |
| Nominal voltage | 125 V AC |
| Article revision | 03 |
| Horizontal pitch | 0.6 Div. |
| Housing material | PA 6.6-FR 20 % GF |
| Pollution degree | 2 |
| Response time tA | ≤ 25 ns |
| Connection method | pluggable |
| Nominal frequency | 50/60 Hz |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Mode of protection | L-N |
| Nominal voltage UN | 120 V AC (TN) |
| TOV behavior at UT | 240 V AC (5 s / withstand mode) |
| Dimensional drawing | |
| Direction of action | L-N / L-PEN |
| Insulating material | PA6.6-FR 20% GF |
| Number of positions | 1 |
| Degree of protection | IP20 |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Overvoltage category | III |
| CTI value of material | 600 |
| Residual voltage Ures | ≤ 0.85 kV (at In) |
| Standards/regulations | DIN VDE 0110-1 / IEC 60664-1 / IEC 61643-11 / UL 1449 |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| IEC power supply system | TN |
| IEC test classification | II |
| Standards/specifications | IEC 61643-11 |
| Power distribution system | Single phase |
| Voltage protection level Up | ≤ 0.85 kV |
| Maximum continuous voltage UC | 175 V AC |
| Surge protection fault message | optical |
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Nominal discharge current In(L-N) | 20 kA |
| Short-circuit current rating ISCCR | 25 kA (for a backup fuse of up to 315 A gG) |
| Max. backup fuse with branch wiring | 315 A (gG) |
| Measured limiting voltage MLV (L-N) | 1510 V |
| Flammability rating according to UL 94 | V-0 |
| Nominal discharge current In(8/20) µs | 20 kA |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Maximum continuous operating voltage MCOV (L-N) | 175 V AC |
Technical specifications and performance data
Installation and operation guide