| Parameter | Value |
|---|---|
| GTIN | 4046356714280 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2801165 |
| (General) | ≤ 1.8 kV (at 40 kA) |
| Catalog page | Page 41 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | (L-) - G |
| Custom tariff number | 85363030 |
| (Ambient conditions) | PV T1 / T2 |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | jet black RAL 9005 |
| Response time tA (General) | ≤ 25 ns |
| SPD Type (Connection data) | 1CA |
| Depth (Key Commercial Data) | 55.3 mm |
| Width (Key Commercial Data) | 17.5 mm |
| EN type (Ambient conditions) | T1 / T2 |
| Height (Key Commercial Data) | 52.4 mm |
| Shock (operation) (Dimensions) | 60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Residual voltage Ures (General) | ≤ 1.4 kV (at In) |
| Degree of protection (Dimensions) | IP20 |
| Nominal voltage (Connection data) | 800 V DC |
| Accessibility (Ambient conditions) | Accessible |
| Mounting type (Ambient conditions) | on base element |
| Vibration (operation) (Dimensions) | 7.5g (5-500 Hz/2.5 h/XYZ) |
| Insulation resistance Riso (General) | > 5 GΩ (at 500 V DC) |
| Mode of protection (Connection data) | (L+) - (L-) |
| Weight per Piece (excluding packing) | 57.420 g |
| Housing material (Ambient conditions) | PA 6.6-FR |
| Voltage protection level Up (General) | ≤ 1.4 kV |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Standby power consumption PC (General) | ≤ 10 mVA |
| Degree of pollution (Ambient conditions) | 2 |
| SPD failure behavior (Ambient conditions) | OCM (Open-circuit mode) |
| Standards/regulations (UL specifications) | EN 50539-11 2013 |
| Installation location (Ambient conditions) | Inside |
| Continuous operating current ICPV (General) | < 20 µA |
| Power distribution system (Connection data) | DC PV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC test classification (Ambient conditions) | PV I / II |
| Short-circuit current rating ISCPV (General) | 2000 A |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Nominal discharge current (8/20) µs (General) | 15 kA |
| Nominal discharge current In (Connection data) | 20 kA |
| Voltage protection rating VPR (Connection data) | 2 kV |
| Maximum discharge current Imax(8/20) µs (General) | 40 kA |
| Maximum continuous operating voltage UCPV (General) | 360 V DC |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Short-circuit current rating (SCCR) (Connection data) | 50 kA |
| Impulse discharge current (10/350) µs, charge (General) | 2.5 As |
| Connection method (Protective circuit DC voltage side (DC)) | pluggable |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Maximum continuous operating voltage MCOV (Connection data) | 800 V DC |
| Impulse discharge current (10/350) µs, peak value limp (General) | 5 kA |
| Impulse discharge current (10/350) µs, specific energy (General) | 6.25 kJ/Ω |
| Installation location of the disconnect device (Ambient conditions) | Internal |
Technical specifications and performance data