| Parameter | Value |
|---|---|
| GTIN | 4046356750196 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2801242 |
| (General) | 130 V DC (5 s / withstand mode) |
| Catalog page | Page 38 (C-4-2017) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| (UL specifications) | EN 61643-11 2012 |
| Custom tariff number | 85366990 |
| (Ambient conditions) | PBT |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | jet black RAL 9005 |
| Response time tA (General) | ≤ 25 ns |
| SPD Type (Connection data) | 1CA |
| Depth (Key Commercial Data) | 67.3 mm |
| Width (Key Commercial Data) | 17.5 mm |
| EN type (Ambient conditions) | T1 / T2 |
| Height (Key Commercial Data) | 47 mm |
| Nominal voltage UN (General) | 60 V AC ±10 % (TN) |
| TOV behavior at UT (General) | 100 V AC (5 s / withstand mode) |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 0.6 mA |
| Shock (operation) (Dimensions) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Residual voltage Ures (General) | ≤ 0.4 kV (at In) |
| Degree of protection (Dimensions) | IP20 |
| Nominal voltage (Connection data) | 60 V DC |
| Mounting type (Ambient conditions) | on base element |
| Vibration (operation) (Dimensions) | 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| Mode of protection (Connection data) | (L+) - (L-) |
| Weight per Piece (excluding packing) | 52.400 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Voltage protection level Up (General) | ≤ 0.4 kV |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Standby power consumption PC (General) | ≤ 45 mVA |
| Maximum continuous voltage UC (General) | 75 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Degree of pollution (Ambient conditions) | 2 |
| Standards/regulations (UL specifications) | IEC 61643-11 2011 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TN-C |
| IEC test classification (Ambient conditions) | I / II |
| Short-circuit current rating ISCCR (General) | 25 kA |
| Connection method (Additional technical data) | pluggable |
| Max. backup fuse with branch wiring (General) | 160 A (gG) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Nominal discharge current In(8/20) µs (General) | 12.5 kA |
| Maximum discharge current Imax(8/20) µs (General) | 30 kA |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Short-circuit current rating (SCCR) (Connection data) | 5 kA |
| Impulse discharge current (10/350) µs, charge (General) | 6.25 As |
| Nominal discharge current In(L+) - (L-) (Connection data) | 20 kA |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Voltage protection rating VPR (L+) - (L-) (Connection data) | 400 V |
| Maximum discharge current Imax(8/20) µs (Protective circuit) | 65 kA |
| Impulse discharge current (10/350) µs, peak value limp (General) | 12.5 kA |
| Impulse discharge current (10/350) µs, specific energy (General) | 39 kJ/Ω |
| Maximum continuous operating voltage MCOV (L+) - (L-) (Connection data) | 100 V DC |