| Parameter | Value |
|---|---|
| GTIN | 4046356811316 |
| Orderkey | 2801532 |
| (General) | 130 V DC (5 s / withstand mode) |
| Catalog page | Page 38 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | (L-) - G |
| Custom tariff number | 85363030 |
| (Ambient conditions) | PBT |
| (UL connection data) | EN 61643-11 2012 |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | DIN rail module, two-section, divisible |
| Color (Ambient conditions) | jet black RAL 9005 |
| Response time tA (General) | ≤ 25 ns |
| SPD Type (Connection data) | 1CA |
| Depth (Key Commercial Data) | 77.5 mm (incl. DIN rail 7.5 mm) |
| Width (Key Commercial Data) | 35.6 mm |
| (Additional technical data) | 4.5 Nm (25 mm² ... 35 mm²) |
| EN type (Ambient conditions) | T1 / T2 |
| Height (Key Commercial Data) | 89.8 mm |
| Nominal voltage UN (General) | 60 V AC ±10 % (TN-S) |
| TOV behavior at UT (General) | 100 V AC (5 s / withstand mode) |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 0.6 mA |
| Shock (operation) (Dimensions) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Rated load current IL (General) | 80 A |
| Residual voltage Ures (General) | ≤ 0.4 kV (at In) |
| Degree of protection (Dimensions) | IP20 (only when all terminal points are used) |
| Nominal voltage (Connection data) | 60 V DC |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Vibration (operation) (Dimensions) | 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| Mode of protection (Connection data) | (L+) - (L-) |
| Weight per Piece (excluding packing) | 255.700 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Tightening torque (UL specifications) | 30 lbf-in. |
| Horizontal pitch (Key Commercial Data) | 2 Div. |
| Standby power consumption PC (General) | ≤ 90 mVA |
| Maximum continuous voltage UC (General) | 75 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Degree of pollution (Ambient conditions) | 2 |
| Screw thread (Additional technical data) | M5 |
| Standards/regulations (UL connection data) | IEC 61643-11 2011 |
| Voltage protection level Up(L-N) (General) | ≤ 0.4 kV |
| Voltage protection level Up(L-PE) (General) | ≤ 0.8 kV |
| Voltage protection level Up(N-PE) (General) | ≤ 0.4 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TN-S |
| IEC test classification (Ambient conditions) | I / II |
| Short-circuit current rating ISCCR (General) | 25 kA |
| Stripping length (Additional technical data) | 16 mm |
| Connection method (Additional technical data) | Fork-type cable lug |
| Max. backup fuse with branch wiring (General) | 160 A (gG) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Tightening torque (Additional technical data) | 3 Nm (1,5 mm² ... 16 mm²) |
| Voltage protection level Up(L+) - PE (General) | ≤ 0.4 kV |
| Voltage protection level Up(L-) - PE (General) | ≤ 0.8 kV |
| Conductor cross section AWG (UL specifications) | 10 ... 2 |
| Nominal discharge current In(8/20) µs (General) | 12.5 kA |
| Voltage protection level Up(L+) - (L-) (General) | ≤ 0.4 kV |
| Maximum discharge current Imax(8/20) µs (General) | 30 kA |
| Total discharge current Itotal(8/20) µs (General) | 50 kA |
| Surge protection fault message (Ambient conditions) | optical |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Total discharge current Itotal(10/350) µs (General) | 12.5 kA |
| Max. backup fuse with V-type through wiring (General) | 80 A (gG - 16 mm²) |
| Short-circuit current rating (SCCR) (Connection data) | 5 kA |
| Nominal discharge current In(L+) - G (Connection data) | 20 kA |
| Nominal discharge current In(L-) - G (Connection data) | 20 kA |
| Conductor cross section AWG (Additional technical data) | 15 ... 2 |
| Voltage protection rating VPR (L-) -G (Connection data) | 600 V |
| Impulse discharge current (10/350) µs, charge (General) | 6.25 As |
| Voltage protection rating VPR (L+) - G (Connection data) | 400 V |
| Conductor cross section solid (Additional technical data) | 1.5 mm² ... 35 mm² |
| Nominal discharge current In(L+) - (L-) (Connection data) | 20 kA |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Voltage protection rating VPR (L+) - (L-) (Connection data) | 400 V |
| Conductor cross section flexible (Additional technical data) | 1.5 mm² ... 16 mm² |
| Maximum discharge current Imax(8/20) µs (Protective circuit) | 65 kA |
| Impulse discharge current (10/350) µs, peak value limp (General) | 12.5 kA |
| Impulse discharge current (10/350) µs, specific energy (General) | 39 kJ/Ω |
| Maximum continuous operating voltage MCOV (L+) - G (Connection data) | 100 V DC |
| Maximum continuous operating voltage MCOV (L-) - G (Connection data) | 100 V DC |
| Maximum continuous operating voltage MCOV (L+) - (L-) (Connection data) | 100 V DC |
Technical specifications and performance data
Installation and operation guide