VAL-MS-T1/T2 1000DC-PV/2+V

VAL-MS-T1/T2 1000DC-PV/2+V 2801160 PHOENIX CONTACT Lightning/surge arrester for 2-pos. isolated 1000 V DC vo..

$0.00USD
4277 in stock
Key Specifications
:PV T2
Note:The device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area.
Type:DIN rail module, two-section, divisible
Color:jet black RAL 9005
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
PV T2
NoteThe device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area.
TypeDIN rail module, two-section, divisible
Colorjet black RAL 9005
Depth65.5 mm
Width53.4 mm
Height90 mm
EN typeT1
Altitude≤ 2000 m (amsl (above mean sea level))
SPD Type4 (for Type 2 photovoltaic applications)
SPD designCombination type
Nom. voltage875 V AC
Screw threadM5
AccessibilityAccessible
Mounting typeDIN rail: 35 mm
Number of portsOne
Horizontal pitch3 Div.
Housing materialPA 6.6-FR
Pollution degree2
Stripping length16 mm
Connection methodScrew connection
Shock (operation)60g (Half sine/11 ms/3x XYZ)
Tightening torque4.5 Nm
Mode of protection(L+) - (L-)
Degree of protectionIP20 (only when all terminal points are used)
Residual current IPE≤ 20 µA DC
SPD failure behaviorOCM (Open-circuit mode)
Installation locationInside
Rated load current IL80 A
Vibration (operation)7.5g (5-500 Hz/2.5 h/XYZ)
IEC test classificationPV T1
Connection configurationY configuration
Response time tA(L-) -PE≤ 25 ns
Standards/specificationsEN 50539-11 2013
Power distribution system1
Response time tA(L+) - PE≤ 25 ns
Insulation resistance Riso> 5 GΩ (at 500 V DC)
Conductor cross section AWG15 ... 2
Open circuit voltage UOCSTC≤ 875 V DC
Response time tA(L+) - (L-)≤ 25 ns
Standby power consumption PC≤ 25 mVA
Residual voltage Ures(L+) - PE≤ 3.5 kV (at In)
Residual voltage Ures(L-) - PE≤ 3.5 kV (at In)
Surge protection fault messageoptical
Ambient temperature (operation)-40 °C ... 80 °C
Permissible humidity (operation)5 % ... 95 %
Residual voltage Ures(L+) - (L-)≤ 3.5 kV (at In)
Continuous operating current ICPV< 20 µA
Conductor cross section solid max.35 mm²
Conductor cross section solid min.1.5 mm²
Short-circuit current rating ISCPV1000 A
Nominal discharge current In(L+) - G20 kA
Nominal discharge current In(L-) - G20 kA
Voltage protection level Up(L+) - PE≤ 3.5 kV
Voltage protection level Up(L-) - PE≤ 3.5 kV
Conductor cross section flexible max.25 mm²
Conductor cross section flexible min.1.5 mm²
Voltage protection rating VPR (L-) -G3 kV
Flammability rating according to UL 94V-0
Voltage protection level Up(L+) - (L-)≤ 3.5 kV
Voltage protection rating VPR (L+) - G3 kV
Ambient temperature (storage/transport)-40 °C ... 80 °C
Nominal discharge current In(L+) - (L-)20 kA
Distance between live and grounded parts8 mm
Maximum continuous operating voltage UCPV1050 V DC
Total discharge current ITotal(8/20) µs40 kA
Voltage protection rating VPR (L+) - (L-)3 kV
Total discharge current ITotal(10/350) µs5 kA
Installation location of the disconnect deviceInternal
Impulse discharge current (10/350)˽µs, charge2.5 As
Nominal discharge current In(8/20) µs (L+) - PE15 kA
Nominal discharge current In(8/20) µs (L-) - PE15 kA
Maximum continuous operating voltage MCOV (L+) - G1050 V DC
Maximum continuous operating voltage MCOV (L-) - G1050 V DC
Maximum discharge current Imax(8/20) µs (L+) - PE40 kA
Maximum discharge current Imax(8/20) µs (L-) - PE40 kA
Nominal discharge current In(8/20) µs (L+) - (L-)15 kA
Maximum discharge current Imax(8/20) µs (L+) - (L-)40 kA
Maximum continuous operating voltage MCOV (L+) - (L-)1050 V DC
Impulse discharge current (10/350) µs, peak value limp5 kA
Impulse discharge current (10/350)˽µs, specific energy6.25 kJ/Ω

Product Description

Lightning surge / current protection device for isolated and grounded 2-pole photovoltaic 1000V DC direct current systems, for rail mounting, 3-pole base element, three plug-in protection elements wit