Key Specifications
GTIN:4055626081601
Orderkey:2906484
Catalog page:Page 59 (C-4-2017)
Packing unit:1 pc
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4055626081601
Orderkey2906484
Catalog pagePage 59 (C-4-2017)
Packing unit1 pc
Note (General)For installation into a touch protected cabinet. For applications with UC> 500 V distances at the side and distances at the connection area must be minimum of 5 mm between different active parts including earthed parts.
Country of originDE (Germany)
Custom tariff number85366990
(Ambient conditions)T2
(Protective circuit)1 A DC
(UL connection data)EN 61643-11 2012
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions)Base element, DIN rail mounting
Color (Ambient conditions)jet black RAL 9005
SPD Type (Connection data)4CA
Depth (Key Commercial Data)51.5 mm (incl. DIN rail 7.5 mm)
Width (Key Commercial Data)71 mm
EN type (Ambient conditions)T2
Height (Key Commercial Data)98.7 mm
(Indicator/remote signaling)4.5 Nm (25 mm² ... 35 mm²)
Nom. voltage (Connection data)690 V AC
Shock (operation) (Dimensions)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Degree of protection (Dimensions)IP20 (only when all terminal points are used)
Screw thread (Protective circuit)M2
Mounting type (Ambient conditions)DIN rail: 35 mm
Vibration (operation) (Dimensions)7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Nominal frequency (Connection data)50/60 Hz
Weight per Piece (excluding packing)293.700 g
Housing material (Ambient conditions)PBT
Operating current (UL specifications)1 A AC
Operating voltage (UL specifications)125 V AC
Stripping length (Protective circuit)7 mm
Tightening torque (UL specifications)4 lbf-in.
Connection method (Protective circuit)Plug-in/screw connection via COMBICON
Horizontal pitch (Key Commercial Data)4 Div.
Operating current (Protective circuit)5 mA AC ... 750 mA AC
Operating voltage (Protective circuit)5 V AC ... 250 V AC
Tightening torque (Protective circuit)0.25 Nm
Switching function (Protective circuit)PDT contact
Degree of pollution (Ambient conditions)2
Number of positions (Ambient conditions)4
Screw thread (Indicator/remote signaling)M5
Standards/regulations (UL connection data)IEC 61643-11 2011
Ambient temperature (operation) (Dimensions)-40 °C ... 80 °C
IEC test classification (Ambient conditions)II
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Stripping length (Indicator/remote signaling)16 mm
Connection method (Indicator/remote signaling)Fork-type cable lug
Nominal frequency fN (Additional descriptions)50 Hz (60 Hz)
Tightening torque (Indicator/remote signaling)3 Nm (1,5 mm² ... 16 mm²)
Conductor cross section AWG (UL specifications)30 ... 14
Rated load current IL (Additional descriptions)80 A
Conductor cross section AWG (Protective circuit)28 ... 16
Tightening torque (UL indicator/remote signaling)30 lbf-in.
Conductor cross section solid (Protective circuit)0.14 mm² ... 1.5 mm²
Surge protection fault message (Ambient conditions)Remote indication contact
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Conductor cross section flexible (Protective circuit)0.14 mm² ... 1.5 mm²
Maximum continuous voltage UC (Additional descriptions)800 V AC
Conductor cross section AWG (Indicator/remote signaling)15 ... 2
Conductor cross section solid (Indicator/remote signaling)1.5 mm² ... 35 mm²
Conductor cross section AWG (UL indicator/remote signaling)10 ... 2
Flammability rating according to UL 94 (Ambient conditions)V-0
Short-circuit current rating ISCCR (Additional descriptions)25 kA
Conductor cross section flexible (Indicator/remote signaling)1.5 mm² ... 16 mm²
Max. backup fuse with branch wiring (Additional descriptions)125 A (gG)
Max. backup fuse with V-type through wiring (Additional descriptions)80 A (gG)

Product Description

Base element for type 2 unloaders from the VALVETRAB MS product series, with remote indication contact. Execution for three-phase power supplies with separate N and PE conduction.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide