

| Parameter | Value |
|---|---|
| GTIN | 4046356280006 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2921284 |
| (General) | 457 V AC (120 min / withstand mode) |
| Catalog page | Page 49 (C-6-2013) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | N-G |
| Custom tariff number | 85363030 |
| (Ambient conditions) | PBT |
| (Protective circuit) | 1 A DC |
| (UL connection data) | EN 61643-11 2012 |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | DIN rail module, two-section, divisible |
| Color (Ambient conditions) | jet black RAL 9005 |
| SPD Type (Connection data) | 4CA |
| Depth (Key Commercial Data) | 77.5 mm (incl. DIN rail 7.5 mm) |
| Width (Key Commercial Data) | 35.6 mm |
| EN type (Ambient conditions) | T2 |
| Height (Key Commercial Data) | 96.8 mm |
| Nominal voltage UN (General) | 240 V AC (TN-S) |
| (Indicator/remote signaling) | 4.5 Nm (25 mm² ... 35 mm²) |
| Nom. voltage (Connection data) | 240 V AC |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 5 µA |
| Shock (operation) (Dimensions) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Rated load current IL (General) | 80 A |
| Response time tA(L-N) (General) | ≤ 25 ns |
| Response time tA(L-PE) (General) | ≤ 100 ns |
| Response time tA(N-PE) (General) | ≤ 100 ns |
| Degree of protection (Dimensions) | IP20 (only when all terminal points are used) |
| Screw thread (Protective circuit) | M2 |
| TOV behavior at UT(L-N) (General) | 480 V AC (5 s / withstand mode) |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| TOV behavior at UT(N-PE) (General) | 1200 V AC (200 ms / withstand mode) |
| Vibration (operation) (Dimensions) | 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| Nominal frequency (Connection data) | 50/60 Hz |
| Mode of protection (Connection data) | L-N |
| Residual voltage Ures(L-N) (General) | ≤ 2 kV (at In) |
| Weight per Piece (excluding packing) | 330.900 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Operating current (UL specifications) | 1 A AC |
| Operating voltage (UL specifications) | 125 V AC |
| Residual voltage Ures(L-PE) (General) | ≤ 2 kV (at In) |
| Residual voltage Ures(N-PE) (General) | ≤ 0.6 kV (at In) |
| Stripping length (Protective circuit) | 7 mm |
| Tightening torque (UL specifications) | 4 lbf-in. |
| Connection method (Protective circuit) | Plug-in/screw connection via COMBICON |
| Horizontal pitch (Key Commercial Data) | 2 Div. |
| Operating current (Protective circuit) | 5 mA AC ... 1.5 A AC |
| Operating voltage (Protective circuit) | 5 V AC ... 250 V AC |
| Standby power consumption PC (General) | ≤ 231 mVA |
| Tightening torque (Protective circuit) | 0.25 Nm |
| Mode of protection (Ambient conditions) | L-N |
| Switching function (Protective circuit) | PDT contact |
| Degree of pollution (Ambient conditions) | 2 |
| Screw thread (Indicator/remote signaling) | M5 |
| Standards/regulations (UL connection data) | IEC 61643-11 2011 |
| Voltage protection level Up(L-N) (General) | ≤ 2 kV |
| Power distribution system (Connection data) | Single phase |
| Voltage protection level Up(L-PE) (General) | ≤ 2 kV |
| Voltage protection level Up(N-PE) (General) | ≤ 1.7 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC power supply system (Ambient conditions) | TT |
| IEC test classification (Ambient conditions) | II |
| Short-circuit current rating ISCCR (General) | 25 kA |
| Max. backup fuse with branch wiring (General) | 250 A (gG) |
| Maximum continuous voltage UC(N-PE) (General) | 264 V AC |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Stripping length (Indicator/remote signaling) | 16 mm |
| Connection method (Indicator/remote signaling) | Fork-type cable lug |
| Tightening torque (Indicator/remote signaling) | 3 Nm (1,5 mm² ... 16 mm²) |
| Conductor cross section AWG (UL specifications) | 30 ... 14 |
| Conductor cross section AWG (Protective circuit) | 28 ... 16 |
| Nominal discharge current In(8/20) µs (General) | 40 kA |
| Tightening torque (UL indicator/remote signaling) | 30 lbf-in. |
| Conductor cross section solid (Protective circuit) | 0.14 mm² ... 1.5 mm² |
| Maximum discharge current Imax(8/20) µs (General) | 80 kA |
| Total discharge current Itotal(8/20) µs (General) | 80 kA |
| Follow current interrupt rating Ifi(N-PE) (General) | 100 A |
| Nominal discharge current In(L-G) (Connection data) | 20 kA |
| Nominal discharge current In(L-N) (Connection data) | 20 kA |
| Nominal discharge current In(N-G) (Connection data) | 20 kA |
| Surge protection fault message (Ambient conditions) | Optical, remote indicator contact |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Total discharge current Itotal(10/350) µs (General) | 5 kA |
| Conductor cross section flexible (Protective circuit) | 0.14 mm² ... 1.5 mm² |
| Max. backup fuse with V-type through wiring (General) | 80 A (gG - 16 mm²) |
| Measured limiting voltage MLV (L-G) (Connection data) | 3730 V |
| Measured limiting voltage MLV (L-N) (Connection data) | 2710 V |
| Measured limiting voltage MLV (N-G) (Connection data) | 2590 V |
| Maximum continuous operating voltage UC(L-N) (General) | 385 V AC |
| Conductor cross section AWG (Indicator/remote signaling) | 15 ... 2 |
| Conductor cross section solid (Indicator/remote signaling) | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG (UL indicator/remote signaling) | 10 ... 2 |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Conductor cross section flexible (Indicator/remote signaling) | 1.5 mm² ... 16 mm² |
| Impulse discharge current (10/350) µs (L-N), charge (General) | 1.25 As |
| Impulse discharge current (10/350) µs (L-PE), charge (General) | 1.25 As |
| Impulse discharge current (10/350) µs (N-PE), charge (General) | 5 As |
| Maximum continuous operating voltage MCOV (L-G) (Connection data) | 385 V AC |
| Maximum continuous operating voltage MCOV (L-N) (Connection data) | 385 V AC |
| Maximum continuous operating voltage MCOV (N-G) (Connection data) | 264 V AC |
| Impulse discharge current (10/350) µs (L-N), specific energy (General) | 1.56 kJ/Ω |
| Impulse discharge current (10/350) µs (L-PE), specific energy (General) | 1.56 kJ/Ω |
| Impulse discharge current (10/350) µs (N-PE), specific energy (General) | 25 kJ/Ω |
| Impulse discharge current (10/350) µs (L-N), peak current value Iimp (General) | 2.5 kA |
| Impulse discharge current (10/350) µs (L-PE), peak current value Iimp (General) | 2.5 kA |
| Impulse discharge current (10/350) µs (N-PE), peak current value Iimp (General) | 10 kA |
Technical specifications and performance data
Installation and operation guide