Service time: Monday to Friday 9:00-18:00
VAL-MS 320/3+1 - VAL-MS 320/3+1 2859178 PHOENIX CONTACT Type 2 surge arrester
In Stock Hot Product

VAL-MS 320/3+1

VAL-MS 320/3+1 2859178 PHOENIX CONTACT Type 2 surge arrester

$0.00USD
4894 in stock
Key Specifications
GTIN:4017918911225
Orderkey:2859178
(General):440 V AC (120 min / safe failure mode)
Catalog page:Page 52 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918911225
Orderkey2859178
(General)440 V AC (120 min / safe failure mode)
Catalog pagePage 52 (C-4-2017)
Packing unit1 pc
Country of originDE (Germany)
(Connection data)N-G
Custom tariff number85363030
(Ambient conditions)PBT
(Protective circuit)4.5 Nm (25 mm² ... 35 mm²)
(UL connection data)EN 61643-11 2012
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions)DIN rail module, two-section, divisible
Color (Ambient conditions)jet black RAL 9005
SPD Type (Connection data)4CA
Depth (Key Commercial Data)65.7 mm (incl. DIN rail 7.5 mm)
Width (Key Commercial Data)71 mm
EN type (Ambient conditions)T2
Height (Key Commercial Data)89.8 mm
Nominal voltage UN (General)240/415 V AC (TN-S)
Nom. voltage (Connection data)240/415 V AC
Nominal frequency fN (General)50 Hz (60 Hz)
Residual current IPE (General)≤ 5 µA
Shock (operation) (Dimensions)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Rated load current IL (General)80 A
Response time tA(L-N) (General)≤ 25 ns
Response time tA(L-PE) (General)≤ 100 ns
Response time tA(N-PE) (General)≤ 100 ns
Degree of protection (Dimensions)IP20 (only when all terminal points are used)
Screw thread (Protective circuit)M5
TOV behavior at UT(L-N) (General)415 V AC (5 s / withstand mode)
Mounting type (Ambient conditions)DIN rail: 35 mm
TOV behavior at UT(N-PE) (General)1200 V AC (200 ms / withstand mode)
Vibration (operation) (Dimensions)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Nominal frequency (Connection data)50/60 Hz
Mode of protection (Connection data)L-L
Residual voltage Ures(L-N) (General)≤ 1.5 kV (at In)
Weight per Piece (excluding packing)386.120 g
Housing material (Ambient conditions)PA 6.6
Residual voltage Ures(L-PE) (General)≤ 1.9 kV (at In)
Residual voltage Ures(N-PE) (General)≤ 0.4 kV (at In)
Stripping length (Protective circuit)16 mm
Tightening torque (UL specifications)30 lbf-in.
Connection method (Protective circuit)Fork-type cable lug
Horizontal pitch (Key Commercial Data)4 Div.
Standby power consumption PC (General)≤ 450 mVA
Tightening torque (Protective circuit)3 Nm (1,5 mm² ... 16 mm²)
Mode of protection (Ambient conditions)L-N
Degree of pollution (Ambient conditions)2
Number of positions (Ambient conditions)4
Standards/regulations (UL connection data)IEC 61643-11 2011
Voltage protection level Up(L-N) (General)≤ 1.5 kV
Power distribution system (Connection data)Wye
Voltage protection level Up(L-PE) (General)≤ 1.9 kV
Voltage protection level Up(N-PE) (General)≤ 1.5 kV
Ambient temperature (operation) (Dimensions)-40 °C ... 80 °C
IEC power supply system (Ambient conditions)TN-S
IEC test classification (Ambient conditions)II
Short-circuit current rating ISCCR (General)25 kA
Max. backup fuse with branch wiring (General)125 A (gG)
Maximum continuous voltage UC(N-PE) (General)260 V AC
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Conductor cross section AWG (UL specifications)10 ... 2
Conductor cross section AWG (Protective circuit)15 ... 2
Nominal discharge current In(8/20) µs (General)20 kA
Conductor cross section solid (Protective circuit)1.5 mm² ... 35 mm²
Maximum discharge current Imax(8/20) µs (General)40 kA
Follow current interrupt rating Ifi(N-PE) (General)100 A
Nominal discharge current In(L-G) (Connection data)20 kA
Nominal discharge current In(L-L) (Connection data)20 kA
Nominal discharge current In(L-N) (Connection data)20 kA
Nominal discharge current In(N-G) (Connection data)20 kA
Surge protection fault message (Ambient conditions)optical
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Conductor cross section flexible (Protective circuit)1.5 mm² ... 16 mm²
Max. backup fuse with V-type through wiring (General)80 A (gG)
Measured limiting voltage MLV (L-G) (Connection data)2720 V
Measured limiting voltage MLV (L-L) (Connection data)2900 V
Measured limiting voltage MLV (L-N) (Connection data)2030 V
Measured limiting voltage MLV (N-G) (Connection data)1370 V
Maximum continuous operating voltage UC(L-N) (General)335 V AC
Maximum continuous operating voltage UC(L-PE) (General)335 V AC
Flammability rating according to UL 94 (Ambient conditions)V-0
Maximum continuous operating voltage MCOV (L-G) (Connection data)320 V AC
Maximum continuous operating voltage MCOV (L-L) (Connection data)640 V AC
Maximum continuous operating voltage MCOV (L-N) (Connection data)320 V AC
Maximum continuous operating voltage MCOV (N-G) (Connection data)260 V AC

Product Description

4-channel surge protection device (3+1 switching), for mounting on NS 35/7.5, voltage 230 V AC
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide