Service time: Monday to Friday 9:00-18:00
VAL-MS/3+1-BE - VAL-MS/3+1-BE 2838885 PHOENIX CONTACT Type 2 surge protection base element
In Stock Hot Product

VAL-MS/3+1-BE

VAL-MS/3+1-BE 2838885 PHOENIX CONTACT Type 2 surge protection base element

$0.00USD
4709 in stock
Key Specifications
GTIN:4017918171940
Orderkey:2838885
Catalog page:Page 58 (C-4-2017)
Packing unit:1 pc
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918171940
Orderkey2838885
Catalog pagePage 58 (C-4-2017)
Packing unit1 pc
Country of originDE (Germany)
Custom tariff number85366990
(Ambient conditions)T2
(Protective circuit)4.5 Nm (25 mm² ... 35 mm²)
(UL connection data)EN 61643-11 2012
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions)Base element, DIN rail mounting
Color (Ambient conditions)jet black RAL 9005
SPD Type (Connection data)4CA
Depth (Key Commercial Data)51.5 mm (incl. DIN rail 7.5 mm)
Width (Key Commercial Data)71 mm
EN type (Ambient conditions)T2
Height (Key Commercial Data)89.8 mm
Nom. voltage (Connection data)690 V AC
Nominal frequency fN (General)50 Hz (60 Hz)
Shock (operation) (Dimensions)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Rated load current IL (General)80 A
Degree of protection (Dimensions)IP20 (only when all terminal points are used)
Screw thread (Protective circuit)M5
Mounting type (Ambient conditions)DIN rail: 35 mm
Vibration (operation) (Dimensions)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Weight per Piece (excluding packing)209.100 g
Housing material (Ambient conditions)PBT
Stripping length (Protective circuit)16 mm
Tightening torque (UL specifications)30 lbf-in.
Connection method (Protective circuit)Fork-type cable lug
Horizontal pitch (Key Commercial Data)4 Div.
Tightening torque (Protective circuit)3 Nm (1,5 mm² ... 16 mm²)
Maximum continuous voltage UC (General)500 V AC
Degree of pollution (Ambient conditions)2
Number of positions (Ambient conditions)4
Standards/regulations (UL connection data)IEC 61643-11 2011
Ambient temperature (operation) (Dimensions)-40 °C ... 80 °C
IEC test classification (Ambient conditions)II
Short-circuit current rating ISCCR (General)25 kA
Max. backup fuse with branch wiring (General)125 A (gG)
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Conductor cross section AWG (UL specifications)10 ... 2
Conductor cross section AWG (Protective circuit)15 ... 2
Conductor cross section solid (Protective circuit)1.5 mm² ... 35 mm²
Surge protection fault message (Ambient conditions)none
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Conductor cross section flexible (Protective circuit)1.5 mm² ... 16 mm²
Max. backup fuse with V-type through wiring (General)80 A (gG)
Flammability rating according to UL 94 (Ambient conditions)V-0

Product Description

Base element for type 2 arresters from the VALVETRAB MS product series. Execution for three-phase power supplies with separate N and PE conduction.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty