| Parameter | Value |
|---|---|
| GTIN | 4055626539942 |
| Orderkey | 1033725 |
| Packing unit | 1 pc |
| Note (General) | The device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area. |
| Country of origin | DE (Germany) |
| (Connection data) | (DC-) - G |
| (UL specifications) | 1 A DC |
| Custom tariff number | 85354000 |
| (Ambient conditions) | PBT-FR |
| Altitude (Dimensions) | ≤ 3000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | DIN rail module, two-section, divisible |
| (Additional descriptions) | ≤ 6 kV (at 30 kA) |
| Color (Ambient conditions) | jet black RAL 9005 |
| SPD Type (Connection data) | 1CA |
| Depth (Key Commercial Data) | 65.7 mm |
| Width (Key Commercial Data) | 53.4 mm |
| (Additional technical data) | 1 A DC |
| EN type (Ambient conditions) | T2 |
| Height (Key Commercial Data) | 98.7 mm |
| (Indicator/remote signaling) | 4.5 Nm (25 mm² ... 35 mm²) |
| Shock (operation) (Dimensions) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Degree of protection (Dimensions) | IP20 (only when all terminal points are used) |
| Nominal voltage (Connection data) | 1500 V DC |
| Accessibility (Ambient conditions) | Accessible |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Vibration (operation) (Dimensions) | 5g (5-500 Hz/2.5 h/XYZ) |
| Mode of protection (Connection data) | (DC+) - (DC-) |
| Weight per Piece (excluding packing) | 337.760 g |
| Housing material (Ambient conditions) | PA 6.6-FR |
| Operating current (UL specifications) | 1 A AC |
| Operating voltage (UL specifications) | 30 V AC |
| Tightening torque (UL specifications) | 4 lbf-in. |
| Horizontal pitch (Key Commercial Data) | 3 Div. |
| Mode of protection (Ambient conditions) | (L+) - (L-) |
| Degree of pollution (Ambient conditions) | 2 |
| Screw thread (Additional technical data) | M2 |
| SPD failure behavior (Ambient conditions) | OCM (Open-circuit mode) |
| Screw thread (Indicator/remote signaling) | M5 |
| Installation location (Ambient conditions) | Inside |
| Response time tA (Additional descriptions) | ≤ 25 ns |
| Standards/regulations (UL connection data) | EN 50539-11 2013 |
| Power distribution system (Connection data) | DC PV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| IEC power supply system (Ambient conditions) | DC |
| IEC test classification (Ambient conditions) | PV II |
| Stripping length (Additional technical data) | 7 mm |
| Connection configuration (Ambient conditions) | Y configuration |
| Connection method (Additional technical data) | Plug-in/screw connection via COMBICON |
| Operating current (Additional technical data) | 1 A AC |
| Operating voltage (Additional technical data) | 30 V AC |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Stripping length (Indicator/remote signaling) | 16 mm |
| Tightening torque (Additional technical data) | 0.25 Nm |
| Connection method (Indicator/remote signaling) | Fork-type cable lug |
| Nominal discharge current In (Connection data) | 10 kA |
| Residual current IPE (Additional descriptions) | ≤ 350 µA DC |
| Switching function (Additional technical data) | PDT contact |
| Tightening torque (Indicator/remote signaling) | 3 Nm (1,5 mm² ... 16 mm²) |
| Conductor cross section AWG (UL specifications) | 30 ... 14 |
| Rated load current IL (Additional descriptions) | 80 A |
| Residual voltage Ures (Additional descriptions) | ≤ 5 kV (at In) |
| Voltage protection rating VPR (Connection data) | 4 kV |
| Tightening torque (UL indicator/remote signaling) | 30 lbf-in. |
| Surge protection fault message (Ambient conditions) | Optical, remote indicator contact |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Short-circuit current rating (SCCR) (Connection data) | 50 kA |
| Voltage protection level Up (Additional descriptions) | ≤ 5 kV |
| Standby power consumption PC (Additional descriptions) | ≤ 250 mVA |
| Conductor cross section AWG (Additional technical data) | 28 ... 16 |
| Conductor cross section AWG (Indicator/remote signaling) | 15 ... 2 |
| Conductor cross section solid (Additional technical data) | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid (Indicator/remote signaling) | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG (UL indicator/remote signaling) | 10 ... 2 |
| Continuous operating current ICPV (Additional descriptions) | < 350 µA |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Maximum continuous operating voltage MCOV (Connection data) | 1500 V DC |
| Conductor cross section flexible (Additional technical data) | 0.14 mm² ... 1.5 mm² |
| Short-circuit current rating ISCPV (Additional descriptions) | 2000 A |
| Conductor cross section flexible (Indicator/remote signaling) | 1.5 mm² ... 16 mm² |
| Distance between live and grounded parts (Ambient conditions) | 8 mm |
| Nominal discharge current (8/20) µs (Additional descriptions) | 15 kA |
| Maximum discharge current Imax(8/20) µs (Additional descriptions) | 30 kA |
| Total discharge current Itotal(8/20) µs (Additional descriptions) | 30 kA |
| Installation location of the disconnect device (Ambient conditions) | Internal |
| Maximum continuous operating voltage UCPV (Additional descriptions) | 1500 V DC |
| Nominal discharge current In(8/20) µs (Protective circuit DC voltage side (DC)) | 20 kA (4x (5x In| 120 s) | 30 min)) |
| Maximum discharge current Imax(8/20) µs (Protective circuit DC voltage side (DC)) | 40 kA |
Technical specifications and performance data