| Parameter | Value |
|---|---|
| GTIN | 4046356298988 |
| Orderkey | 2920528 |
| Catalog page | Page 58 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85366990 |
| (Ambient conditions) | T2 |
| (Protective circuit) | 4.5 Nm (25 mm² ... 35 mm²) |
| (UL connection data) | EN 61643-11 2012 |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Type (Ambient conditions) | Base element, DIN rail mounting |
| Color (Ambient conditions) | jet black RAL 9005 |
| SPD Type (Connection data) | 4CA |
| Depth (Key Commercial Data) | 51.5 mm (incl. DIN rail 7.5 mm) |
| Width (Key Commercial Data) | 35.6 mm |
| EN type (Ambient conditions) | T2 |
| Height (Key Commercial Data) | 89.8 mm |
| Nom. voltage (Connection data) | 690 V AC |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Shock (operation) (Dimensions) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Rated load current IL (General) | 80 A |
| Degree of protection (Dimensions) | IP20 (only when all terminal points are used) |
| Screw thread (Protective circuit) | M5 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Vibration (operation) (Dimensions) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| Weight per Piece (excluding packing) | 159.400 g |
| Housing material (Ambient conditions) | PBT |
| Stripping length (Protective circuit) | 16 mm |
| Tightening torque (UL specifications) | 30 lbf-in. |
| Connection method (Protective circuit) | Fork-type cable lug |
| Horizontal pitch (Key Commercial Data) | 2 Div. |
| Tightening torque (Protective circuit) | 3 Nm (1,5 mm² ... 16 mm²) |
| Maximum continuous voltage UC (General) | 500 V AC |
| Degree of pollution (Ambient conditions) | 2 |
| Number of positions (Ambient conditions) | 2 |
| Standards/regulations (UL connection data) | IEC 61643-11 2011 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 80 °C |
| IEC test classification (Ambient conditions) | II |
| Short-circuit current rating ISCCR (General) | 25 kA |
| Max. backup fuse with branch wiring (General) | 200 A (gG) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Conductor cross section AWG (UL specifications) | 10 ... 2 |
| Conductor cross section AWG (Protective circuit) | 15 ... 2 |
| Conductor cross section solid (Protective circuit) | 1.5 mm² ... 35 mm² |
| Surge protection fault message (Ambient conditions) | none |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Conductor cross section flexible (Protective circuit) | 1.5 mm² ... 16 mm² |
| Max. backup fuse with V-type through wiring (General) | 80 A (gG) |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
Technical specifications and performance data