Service time: Monday to Friday 9:00-18:00
TTC-6P-3-HF-12DC-PT-I - TTC-6P-3-HF-12DC-PT-I 1065313 PHOENIX CONTACT Surge protection, consisting of protective plug and base eleme..
In Stock Hot Product

TTC-6P-3-HF-12DC-PT-I

TTC-6P-3-HF-12DC-PT-I 1065313 PHOENIX CONTACT Surge protection, consisting of protective plug and base eleme..

$0.00USD
4120 in stock
Key Specifications
:C2
Note:2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Type:DIN rail module, two-section, divisible
Depth:100 mm (incl. DIN rail 7.5 mm)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
C2
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012
TypeDIN rail module, two-section, divisible
Depth100 mm (incl. DIN rail 7.5 mm)
Width6.2 mm +0.1 mm
Height105.8 mm
Altitude≤ 4000 m (amsl)
Product typeSurge protection for information technology
Mounting typeDIN rail: TH 35 - 7.5 mm
Rated current600 mA (56 °C)
Product familyTERMITRAB complete
Open side panelNo
Article revision04
Housing materialPBT
Pollution degree2
Connection methodPush-in connection
Nominal voltage UN12 V DC
Dimensional drawing
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Insulating materialPBT
Resistance per path1.65 Ω ±20 %
Capacity (Core-Core)typ. 32 pF
Color (Base element)gray (RAL 7042)
Degree of protectionIP20
Overvoltage categoryIII
Residual current IPE≤ 200 µA
Capacity (Core-Earth)typ. 32 pF
Color (Male connector)light gray (RAL 7035)
IEC test classificationC1
Standards/specificationsIEC 61643-21
Input attenuation aE, sym.typ. 0.3 dB (≤ 8.7 MHz/150 Ω)
Max. required back-up fuse630 mA (FF)
Conductor cross section AWG24 ... 12
Input attenuation aE, asym.typ. 0.3 dB (≤ 10.5 MHz / 150 Ω)
Response time tA(line-line)≤ 1 ns
Pulse reset time (line-line)≤ 30 ms
Response time tA(line-earth)≤ 1 ns
Conductor cross section rigid0.2 mm² ... 4 mm²
Maximum continuous voltage UC15 V DC
Pulse reset time (line-earth)≤ 30 ms
Impulse durability (line-line)C1 - 1 kV / 500 A
Surge protection fault messageoptical
Ambient temperature (operation)-40 °C ... 85 °C
Impulse durability (line-earth)C1 - 1 kV / 500 A
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Permissible humidity (operation)5 % ... 95 %
Operating effective current ICat UC≤ 100 µA
Flammability rating according to UL 94V-0
Voltage protection level Up(line-line)≤ 145 V (C1 - 1 kV / 500 A)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Voltage protection level Up(line-earth)≤ 80 V (C1 - 1 kV / 500 A)
Total discharge current Itotal(8/20) µs10 kA
Voltage protection level Upstatic (line-line)≤ 40 V (C1 - 1 kV / 500 A)
Voltage protection level Upstatic (line-earth)≤ 40 V (C1 - 1 kV / 500 A)
Max. total discharge current Itotal max(8/20) µs20 kA (1x)
Nominal discharge current In(8/20) µs (line-line)5 kA
Cut-off frequency fg (3 dB), sym. in 150 Ω systemtyp. 60 MHz
Nominal discharge current In(8/20) µs (line-ground)5 kA
Pulse discharge current Iimp(10/350) µs (line-line)0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω systemtyp. 60 MHz

Product Description

Surge protection, consisting of protective plug and base element, with integrated status indicator for three signal wires with common reference potential. For HF applications and telecommunications in
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top