| Parameter | Value |
|---|---|
| GTIN | 4055626722733 |
| Orderkey | 1064665 |
| (General) | D1 - 500 A |
| (Drawings) | |
| Catalog page | Page 158 (C-4-2019) |
| Packing unit | 1 |
| Depth (Drawings) | 100 mm (incl. DIN rail 7.5 mm) |
| Width (Drawings) | 6.2 mm +0.1 mm |
| ETIM 5.0 (eCl@ss) | EC000943 |
| ETIM 6.0 (eCl@ss) | EC000943 |
| ETIM 7.0 (eCl@ss) | EC000943 |
| Height (Drawings) | 105.8 mm |
| (Connection data) | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
| Custom tariff number | 85363010 |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Rated current (General) | 5 A (55 °C) |
| UL, USA/Canada (General) | Class I, Div. 2, Groups A, B, C, D T4A |
| (Conformity / approvals) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Type (Ambient conditions) | DIN rail module, two-section, divisible |
| Color (Ambient conditions) | sky blue RAL 5015 |
| (Standards and Regulations) | -40 °C ... 50 °C (T4 / 135 °C) |
| Nominal voltage UN (General) | 24 V DC |
| eCl@ss 8.0 (Classifications) | 27130807 |
| eCl@ss 9.0 (Classifications) | 27130807 |
| Resistance per path (General) | < 0.1 Ω |
| Capacity (line-line) (General) | typ. 30 pF |
| Dimensional drawing (Drawings) | |
| Residual current IPE (General) | ≤ 1 µA |
| Capacity (line-earth) (General) | typ. 30 pF |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C1 |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | DIN rail: TH 35 - 7.5 mm |
| China RoHS (Conformity / approvals) | Environmentally Friendly Use Period = 50 |
| REACh SVHC (Conformity / approvals) | Lead 7439-92-1 |
| Input attenuation aE, sym. (General) | typ. 0.3 dB (≤ 12 MHz / 150 Ω) |
| Max. required back-up fuse (General) | 5 A (F) |
| Housing material (Ambient conditions) | PBT |
| Response time tA(line-line) (General) | ≤ 1 ns |
| Stripping length (Protective circuit) | 8 mm |
| Connection method (Protective circuit) | Screw connection |
| Pulse reset time (line-line) (General) | ≤ 30 ms |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Tightening torque (Protective circuit) | 0.5 Nm ... 0.6 Nm |
| Maximum continuous voltage UC (General) | 30 V DC |
| Pulse reset time (line-earth) (General) | ≤ 500 ms |
| Direction of action (Ambient conditions) | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Impulse durability (line-line) (General) | C1 - 1 kV / 500 A |
| Impulse durability (line-earth) (General) | C1 - 1 kV / 500 A |
| Standards/specifications (Connection data) | EN 60079-0 2012 + A11:2013 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Operating effective current ICat UC (General) | ≤ 5 µA |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Voltage protection level Up(line-line) (General) | ≤ 68 V (C1 - 1 kV/500 A) |
| Max. input current Ii (Standards and Regulations) | 400 mA (T4 / ≤ 50 °C) |
| Max. input voltage Ui (Standards and Regulations) | 30 V DC |
| Voltage protection level Up(line-earth) (General) | ≤ 700 V (C1 - 1 kV/500 A) |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Total discharge current Itotal(8/20) µs (General) | 10 kA |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Max. internal inductance Li (Standards and Regulations) | negligible |
| Maximum inner capacitance Ci (Standards and Regulations) | negligible |
| Ambient temperature (operation) (Standards and Regulations) | -40 °C ... 35 °C (T6 / 85 °C) |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Nominal discharge current In(8/20) µs (line-line) (General) | 0.5 kA |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General) | typ. 60 MHz |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) (General) | 0.5 kA |
Technical specifications and performance data