Service time: Monday to Friday 9:00-18:00
TTC-6P-3-EX-24DC-UT-I - TTC-6P-3-EX-24DC-UT-I 1064665 PHOENIX CONTACT Surge protection, consisting of protective plug and base eleme..
In Stock Hot Product

TTC-6P-3-EX-24DC-UT-I

TTC-6P-3-EX-24DC-UT-I 1064665 PHOENIX CONTACT Surge protection, consisting of protective plug and base eleme..

$0.00USD
3957 in stock
Key Specifications
GTIN:4055626722733
Orderkey:1064665
(General):D1 - 500 A
(Drawings):
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4055626722733
Orderkey1064665
(General)D1 - 500 A
(Drawings)
Catalog pagePage 158 (C-4-2019)
Packing unit1
Depth (Drawings)100 mm (incl. DIN rail 7.5 mm)
Width (Drawings)6.2 mm +0.1 mm
ETIM 5.0 (eCl@ss)EC000943
ETIM 6.0 (eCl@ss)EC000943
ETIM 7.0 (eCl@ss)EC000943
Height (Drawings)105.8 mm
(Connection data)IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Custom tariff number85363010
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Rated current (General)5 A (55 °C)
UL, USA/Canada (General)Class I, Div. 2, Groups A, B, C, D T4A
(Conformity / approvals)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Type (Ambient conditions)DIN rail module, two-section, divisible
Color (Ambient conditions)sky blue RAL 5015
(Standards and Regulations)-40 °C ... 50 °C (T4 / 135 °C)
Nominal voltage UN (General)24 V DC
eCl@ss 8.0 (Classifications)27130807
eCl@ss 9.0 (Classifications)27130807
Resistance per path (General)< 0.1 Ω
Capacity (line-line) (General)typ. 30 pF
Dimensional drawing (Drawings)
Residual current IPE (General)≤ 1 µA
Capacity (line-earth) (General)typ. 30 pF
Degree of protection (Dimensions)IP20
IEC test classification (General)C1
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)DIN rail: TH 35 - 7.5 mm
China RoHS (Conformity / approvals)Environmentally Friendly Use Period = 50
REACh SVHC (Conformity / approvals)Lead 7439-92-1
Input attenuation aE, sym. (General)typ. 0.3 dB (≤ 12 MHz / 150 Ω)
Max. required back-up fuse (General)5 A (F)
Housing material (Ambient conditions)PBT
Response time tA(line-line) (General)≤ 1 ns
Stripping length (Protective circuit)8 mm
Connection method (Protective circuit)Screw connection
Pulse reset time (line-line) (General)≤ 30 ms
Response time tA(line-earth) (General)≤ 100 ns
Tightening torque (Protective circuit)0.5 Nm ... 0.6 Nm
Maximum continuous voltage UC (General)30 V DC
Pulse reset time (line-earth) (General)≤ 500 ms
Direction of action (Ambient conditions)Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Impulse durability (line-line) (General)C1 - 1 kV / 500 A
Impulse durability (line-earth) (General)C1 - 1 kV / 500 A
Standards/specifications (Connection data)EN 60079-0 2012 + A11:2013
Ambient temperature (operation) (Dimensions)-40 °C ... 85 °C
Operating effective current ICat UC (General)≤ 5 µA
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Conductor cross section AWG (Protective circuit)24 ... 12
Voltage protection level Up(line-line) (General)≤ 68 V (C1 - 1 kV/500 A)
Max. input current Ii (Standards and Regulations)400 mA (T4 / ≤ 50 °C)
Max. input voltage Ui (Standards and Regulations)30 V DC
Voltage protection level Up(line-earth) (General)≤ 700 V (C1 - 1 kV/500 A)
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General)10 kA
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 85 °C
Conductor cross section flexible (Protective circuit)0.2 mm² ... 2.5 mm²
Max. internal inductance Li (Standards and Regulations)negligible
Maximum inner capacitance Ci (Standards and Regulations)negligible
Ambient temperature (operation) (Standards and Regulations)-40 °C ... 35 °C (T6 / 85 °C)
Flammability rating according to UL 94 (Ambient conditions)V-0
Nominal discharge current In(8/20) µs (line-line) (General)0.5 kA
Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General)typ. 60 MHz
Nominal discharge current In(8/20) µs (line-earth) (General)5 kA
Pulse discharge current Iimp(10/350) µs (line-earth) (General)0.5 kA

Product Description

Surge protection, consisting of plug-in protection and base element, with integrated status indication for a floating, HART-capable 3-wire intrinsically safe signal circuit.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Technical Details

Dimensional drawing

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide