Service time: Monday to Friday 9:00-18:00
TTC-6P-2X1-M-24DC-UT-I - TTC-6P-2X1-M-24DC-UT-I 2906741 PHOENIX CONTACT Surge protection, consisting of protective plug and base elem..
In Stock Hot Product

TTC-6P-2X1-M-24DC-UT-I

TTC-6P-2X1-M-24DC-UT-I 2906741 PHOENIX CONTACT Surge protection, consisting of protective plug and base elem..

$0.00USD
3203 in stock
Key Specifications
:C2
Note:2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Type:DIN rail module, two-section, divisible
Depth:100 mm (incl. DIN rail 7.5 mm)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
C2
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012
TypeDIN rail module, two-section, divisible
Depth100 mm (incl. DIN rail 7.5 mm)
Width6.2 mm +0.1 mm
Height105.8 mm
Altitude≤ 4000 m (amsl)
Product typeSurge protection for MCR technology
Screw threadM3
Mounting typeDIN rail: TH 35 - 7.5 mm
Rated current600 mA (56 °C)
Product familyTERMITRAB complete
Open side panelNo
Article revision04
Housing materialPBT
Pollution degree2
Connection methodScrew connection
Tightening torque0.5 Nm ... 0.6 Nm
Nominal voltage UN24 V DC
Dimensional drawing
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Insulating materialPBT
Resistance per path1.65 Ω ±20 %
Color (Base element)gray (RAL 7042)
Degree of protectionIP20
Overvoltage categoryIII
Residual current IPE≤ 10 µA
Capacity (Core-Earth)typ. 2.2 nF
Color (Male connector)light gray (RAL 7035)
IEC test classificationC1
Standards/specificationsIEC 61643-21
Max. required back-up fuse630 mA (FF)
Conductor cross section AWG24 ... 12
Input attenuation aE, asym.typ. 0.3 dB (≤ 270 kHz/150 Ω)
Response time tA(line-earth)≤ 1 ns
Conductor cross section rigid0.2 mm² ... 4 mm²
Maximum continuous voltage UC30 V DC
Pulse reset time (line-earth)≤ 300 ms
Surge protection fault messageoptical
Ambient temperature (operation)-40 °C ... 85 °C
Impulse durability (line-earth)C1 - 1 kV / 500 A
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Permissible humidity (operation)5 % ... 95 %
Operating effective current ICat UC≤ 5 µA
Flammability rating according to UL 94V-0
Ambient temperature (storage/transport)-40 °C ... 85 °C
Voltage protection level Up(line-earth)≤ 140 V (C1 - 1 kV / 500 A)
Total discharge current Itotal(8/20) µs10 kA
Voltage protection level Upstatic (line-earth)≤ 55 V (C1 - 1 kV / 500 A)
Max. total discharge current Itotal max(8/20) µs20 kA (1x)
Nominal discharge current In(8/20) µs (line-ground)5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω systemtyp. 960 kHz

Product Description

Surge protection, consisting of plug-in protection and base element, with integrated status display and disconnector blade for two signal conductors with common reference potential, e.g. digital INPUT
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top