Service time: Monday to Friday 9:00-18:00
TTC-6P-1X2-M-EX-24DC-UT-I - TTC-6P-1X2-M-EX-24DC-UT-I 2906824 PHOENIX CONTACT Surge protection, consisting of protective plug and base e..
In Stock Hot Product

TTC-6P-1X2-M-EX-24DC-UT-I

TTC-6P-1X2-M-EX-24DC-UT-I 2906824 PHOENIX CONTACT Surge protection, consisting of protective plug and base e..

$0.00USD
4155 in stock
Key Specifications
GTIN:4055626135861
Orderkey:2906824
(General):D1 - 500 A
(Drawings):
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4055626135861
Orderkey2906824
(General)D1 - 500 A
(Drawings)
Catalog pagePage 152 (C-4-2019)
Packing unit1 pc
Depth (Drawings)100 mm (incl. DIN rail 7.5 mm)
UNSPSC 11 (ETIM)39121610
Width (Drawings)6.2 mm +0.1 mm
Country of originDE (Germany)
ETIM 3.0 (eCl@ss)EC000943
ETIM 4.0 (eCl@ss)EC000943
ETIM 5.0 (eCl@ss)EC000943
ETIM 6.0 (eCl@ss)EC000943
ETIM 7.0 (eCl@ss)EC000943
Height (Drawings)105.8 mm
(Connection data)IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Diagram (Drawings)
UNSPSC 13.2 (ETIM)39121620
UNSPSC 18.0 (ETIM)39121620
UNSPSC 19.0 (ETIM)39121620
UNSPSC 20.0 (ETIM)39121620
UNSPSC 21.0 (ETIM)39121620
UNSPSC 6.01 (ETIM)30212010
UNSPSC 12.01 (ETIM)39121610
Custom tariff number85363010
Pictogram (Drawings)
UNSPSC 7.0901 (ETIM)39121610
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Rated current (General)600 mA (40 °C)
UL, USA/Canada (General)Class I, Div. 2, Groups A, B, C, D T4A
(Conformity / approvals)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Type (Ambient conditions)DIN rail module, two-section, divisible
Color (Ambient conditions)sky blue RAL 5015
(Standards and Regulations)-40 °C ... 50 °C (T4 / 135 °C)
Nominal voltage UN (General)24 V DC
eCl@ss 4.0 (Classifications)27140201
eCl@ss 4.1 (Classifications)27130801
eCl@ss 5.0 (Classifications)27130801
eCl@ss 5.1 (Classifications)27130801
eCl@ss 6.0 (Classifications)27130800
eCl@ss 7.0 (Classifications)27130807
eCl@ss 8.0 (Classifications)27130807
eCl@ss 9.0 (Classifications)27130807
Resistance per path (General)1.65 Ω ±20 %
Capacity (line-line) (General)typ. 2 nF
Residual current IPE (General)≤ 1 µA
Degree of protection (Dimensions)IP20
IEC test classification (General)C1
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)DIN rail: TH 35 - 7.5 mm
China RoHS (Conformity / approvals)Environmentally Friendly Use Period = 50
REACh SVHC (Conformity / approvals)Lead 7439-92-1
Input attenuation aE, sym. (General)typ. 0.3 dB (≤ 250 kHz / 150 Ω)
Max. required back-up fuse (General)630 mA (FF)
Weight per Piece (excluding packing)60.000 g
Housing material (Ambient conditions)PBT
Response time tA(line-line) (General)≤ 1 ns
Stripping length (Protective circuit)8 mm
Connection method (Protective circuit)Screw connection
Pulse reset time (line-line) (General)≤ 700 ms
Response time tA(line-earth) (General)≤ 100 ns
Tightening torque (Protective circuit)0.5 Nm ... 0.6 Nm
Maximum continuous voltage UC (General)30 V DC
Pulse reset time (line-earth) (General)≤ 30 ms
Direction of action (Ambient conditions)Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Impulse durability (line-line) (General)C1 - 1 kV / 500 A
Surge protection fault message (General)optical
Impulse durability (line-earth) (General)C1 - 1 kV / 500 A
Standards/specifications (Connection data)EN 60079-0 2012 + A11:2013
Ambient temperature (operation) (Dimensions)-40 °C ... 85 °C
Operating effective current ICat UC (General)≤ 5 µA
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Conductor cross section AWG (Protective circuit)24 ... 12
Voltage protection level Up(line-line) (General)≤ 55 V (C1 - 1 kV/500 A)
Max. input current Ii (Standards and Regulations)400 mA (T4 / ≤ 50 °C)
Max. input voltage Ui (Standards and Regulations)30 V DC
Voltage protection level Up(line-earth) (General)≤ 900 V (C1 - 1 kV/500 A)
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General)10 kA
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 85 °C
Conductor cross section flexible (Protective circuit)0.2 mm² ... 2.5 mm²
Max. internal inductance Li (Standards and Regulations)negligible
Voltage protection level Upstatic (line-line) (General)≤ 50 V (C1 - 1 kV/500 A)
Insulation voltage to ground (Standards and Regulations)> 180 V DC
Maximum inner capacitance Ci (Standards and Regulations)negligible
Voltage protection level Upstatic (line-earth) (General)≤ 900 V (C1 - 1 kV/500 A)
Ambient temperature (operation) (Standards and Regulations)-40 °C ... 35 °C (T6 / 85 °C)
Flammability rating according to UL 94 (Ambient conditions)V-0
Nominal discharge current In(8/20) µs (line-line) (General)5 kA
Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General)typ. 940 kHz
Nominal discharge current In(8/20) µs (line-earth) (General)5 kA
Pulse discharge current Iimp(10/350) µs (line-line) (General)0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth) (General)0.5 kA

Product Description

Surge protection, consisting of plug-in protection and base element, with integrated status indication and disconnector blade for a potential-free 2-wire Ex i signal circuit, e.g. current loop 0(4) ..
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Technical Details

Diagram

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top