Service time: Monday to Friday 9:00-18:00
TTC-6-GDT-C-24AC-UT-I - TTC-6-GDT-C-24AC-UT-I 2906842 PHOENIX CONTACT Coarse surge protection with integrated status indicator for a..
In Stock Hot Product

TTC-6-GDT-C-24AC-UT-I

TTC-6-GDT-C-24AC-UT-I 2906842 PHOENIX CONTACT Coarse surge protection with integrated status indicator for a..

$0.00USD
4420 in stock
Key Specifications
:C2
Note:2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Type:DIN rail module, one-piece
Color:gray (RAL 7042)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
C2
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012
TypeDIN rail module, one-piece
Colorgray (RAL 7042)
Depth69.5 mm (incl. DIN rail 7.5 mm)
Width6.2 mm
Height92 mm
Altitude≤ 4000 m (amsl)
Product typeSurge protection for MCR technology
Screw threadM3
Mounting typeDIN rail: 35 mm
Rated current1 A DC (60 °C)
Product familyTERMITRAB complete
Open side panelYes
Article revision08
Housing materialPBT
Pollution degree2
Connection methodScrew connection
Tightening torque0.5 Nm ... 0.6 Nm
Nominal voltage UN24 V AC
Dimensional drawing
Direction of actionLine-Earth Ground
Insulating materialPBT
Resistance per path≤ 100 mΩ
Degree of protectionIP20 (with end cover)
Overvoltage categoryIII
Residual current IPE≤ 1 µA
Capacity (Core-Earth)5 pF
IEC test classificationC1
Standards/specificationsIEC 61643-21
Conductor cross section AWG24 ... 12
Input attenuation aE, asym.typ. 0.3 dB (≤ 8 MHz/150 Ω)
Response time tA(line-earth)≤ 100 ns
Conductor cross section rigid0.2 mm² ... 4 mm²
Maximum continuous voltage UC28 V DC
Pulse reset time (line-earth)≤ 1 ms
Surge protection fault messageoptical
Ambient temperature (operation)-40 °C ... 85 °C
Impulse durability (line-earth)C1 - 1 kA
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Permissible humidity (operation)5 % ... 95 %
Operating effective current ICat UC≤ 1 µA
Flammability rating according to UL 94V-0
Ambient temperature (storage/transport)-40 °C ... 85 °C
Voltage protection level Up(line-earth)≤ 800 V (C1 - 2 kV)
Nominal discharge current In(8/20) µs (line-ground)5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ω systemtyp. 130 MHz
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω systemtyp. 25 MHz

Product Description

Sufficient surge protection with integrated status indication for a signal conductor with grounded reference potential.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top