Key Specifications
:C2
Note:2000 + A1:2008 + A2:2012
Type:DIN rail module, one-piece
Color:gray (RAL 7042)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
C2
Note2000 + A1:2008 + A2:2012
TypeDIN rail module, one-piece
Colorgray (RAL 7042)
Depth83.5 mm (incl. DIN rail 7.5 mm)
Width6.2 mm +0.1 mm
Height105.8 mm
Altitude≤ 4000 m (amsl)
Product typeSurge protection for information technology
Mounting typeDIN rail: TH 35 - 7.5 mm
Rated current600 mA (40 °C)
Product familyTERMITRAB complete
Open side panelNo
Article revision02
Housing materialPBT
Pollution degree2
Connection methodPush-in connection
Nominal voltage UN24 V AC
Dimensional drawing
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Insulating materialPBT
Resistance per path1.65 Ω ±20 %
Capacity (Core-Core)typ. 25 pF
Degree of protectionIP20
Overvoltage categoryIII
Residual current IPE≤ 1 µA
Capacity (Core-Earth)typ. 50 pF
IEC test classificationC1
Standards/specificationsIEC 61643-21
Input attenuation aE, sym.typ. 0.3 dB (≤ 10 MHz/150 Ω)
Max. required back-up fuse630 mA (FF)
Conductor cross section AWG24 ... 12
Response time tA(line-line)≤ 1 ms
Capacity (line-signalground)typ. 25 pF
Response time tA(line-earth)≤ 55 ms
Conductor cross section rigid0.2 mm² ... 4 mm²
Maximum continuous voltage UC43 V DC
Impulse durability (line-line)C1 - 1 kV / 500 A
Surge protection fault messageoptical
Ambient temperature (operation)-40 °C ... 85 °C
Impulse durability (line-earth)C1 - 1 kV / 500 A
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Flammability rating according to UL 94V-0
Impulse durability (line-signalground)C1 - 1 kV / 500 A
Nominal discharge current In(8/20) µs10 kA
Voltage protection level Up(line-line)≤ 80 V (C1 - 1 kV / 500 A)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Voltage protection level Up(line-earth)≤ 900 V (C1 - 1 kV / 500 A)
Pulse discharge current Iimp(10/350) µs2.5 kA
Total discharge current Itotal(8/20) µs10 kA
Cut-off frequency fg (3 dB), sym. in 150 Ω systemtyp. 60 MHz

Product Description