Service time: Monday to Friday 9:00-18:00
TT-UKK5-M/ 48DC - TT-UKK5-M/ 48DC 2795973 PHOENIX CONTACT Surge protection device
In Stock Hot Product

TT-UKK5-M/ 48DC

TT-UKK5-M/ 48DC 2795973 PHOENIX CONTACT Surge protection device

$0.00USD
4689 in stock
Key Specifications
GTIN:4017918073237
Note:Made to Order (non-returnable)
Orderkey:2795973
(General):37 V AC
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918073237
NoteMade to Order (non-returnable)
Orderkey2795973
(General)37 V AC
Catalog pagePage 99 (C-6-2013)
Packing unit50 pc
Country of originGR (Greece)
(Connection data)DIN EN 61643-21 2002
Custom tariff number85363010
Rated current (General)12 A (45°C)
Type (Ambient conditions)Double-level terminal block with disconnect knife
Color (Ambient conditions)black
Depth (Key Commercial Data)68 mm
Width (Key Commercial Data)6.2 mm
Height (Key Commercial Data)80 mm
Nominal voltage UN (General)48 V DC
Capacity (line-line) (General)≤ 0.85 nF
VDE requirement class (General)C3
Degree of protection (Dimensions)IP20
IEC test classification (General)C3
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)DIN rail: 35 mm
Weight per Piece (excluding packing)25.590 g
Housing material (Ambient conditions)PA
Response time tA(line-line) (General)≤ 1 ns
Stripping length (Protective circuit)8 mm
Connection method (Protective circuit)Screw connection
Tightening torque (Protective circuit)0.8 Nm
Maximum continuous voltage UC (General)53 V DC
Standards/regulations (Connection data)IEC 61643-21
Direction of action (Ambient conditions)Line-Line
Impulse durability (line-line) (General)C3 - 10 A
Number of positions (Ambient conditions)1
Surge protection fault message (General)none
Connection method IN (Protective circuit)Screw terminal blocks
Connection method OUT (Protective circuit)Screw terminal blocks
Standards/specifications (Connection data)IEC 61643-21 2000
Residual voltage at In(line-line) (General)≤ 111 V
Ambient temperature (operation) (Dimensions)-40 °C ... 85 °C
Operating effective current ICat UC (General)≤ 5 µA
Conductor cross section AWG (Protective circuit)24 ... 12
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General)90 A
Conductor cross section flexible (Protective circuit)0.2 mm² ... 4 mm²
Flammability rating according to UL 94 (Ambient conditions)V-2
Nominal discharge current In(8/20) µs (line-line) (General)90 A
Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General)typ. 3.8 MHz
Nominal pulse current Ian (10/1000) µs (line-line) (General)17.7 A
Output voltage limitation at 1 kV/µs (line-line) static (General)≤ 80 V
Max. discharge current Imax(8/20) µs maximum (line-line) (General)90 A
Standards for cearances and creepage distances (Ambient conditions)VDE 0110-1

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top