| Parameter | Value |
|---|---|
| GTIN | 4017918073237 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2795973 |
| (General) | 37 V AC |
| Catalog page | Page 99 (C-6-2013) |
| Packing unit | 50 pc |
| Country of origin | GR (Greece) |
| (Connection data) | DIN EN 61643-21 2002 |
| Custom tariff number | 85363010 |
| Rated current (General) | 12 A (45°C) |
| Type (Ambient conditions) | Double-level terminal block with disconnect knife |
| Color (Ambient conditions) | black |
| Depth (Key Commercial Data) | 68 mm |
| Width (Key Commercial Data) | 6.2 mm |
| Height (Key Commercial Data) | 80 mm |
| Nominal voltage UN (General) | 48 V DC |
| Capacity (line-line) (General) | ≤ 0.85 nF |
| VDE requirement class (General) | C3 |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C3 |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Weight per Piece (excluding packing) | 25.590 g |
| Housing material (Ambient conditions) | PA |
| Response time tA(line-line) (General) | ≤ 1 ns |
| Stripping length (Protective circuit) | 8 mm |
| Connection method (Protective circuit) | Screw connection |
| Tightening torque (Protective circuit) | 0.8 Nm |
| Maximum continuous voltage UC (General) | 53 V DC |
| Standards/regulations (Connection data) | IEC 61643-21 |
| Direction of action (Ambient conditions) | Line-Line |
| Impulse durability (line-line) (General) | C3 - 10 A |
| Number of positions (Ambient conditions) | 1 |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | Screw terminal blocks |
| Connection method OUT (Protective circuit) | Screw terminal blocks |
| Standards/specifications (Connection data) | IEC 61643-21 2000 |
| Residual voltage at In(line-line) (General) | ≤ 111 V |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Operating effective current ICat UC (General) | ≤ 5 µA |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Total discharge current Itotal(8/20) µs (General) | 90 A |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 4 mm² |
| Flammability rating according to UL 94 (Ambient conditions) | V-2 |
| Nominal discharge current In(8/20) µs (line-line) (General) | 90 A |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General) | typ. 3.8 MHz |
| Nominal pulse current Ian (10/1000) µs (line-line) (General) | 17.7 A |
| Output voltage limitation at 1 kV/µs (line-line) static (General) | ≤ 80 V |
| Max. discharge current Imax(8/20) µs maximum (line-line) (General) | 90 A |
| Standards for cearances and creepage distances (Ambient conditions) | VDE 0110-1 |