| Parameter | Value |
|---|---|
| GTIN | 4017918938147 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2858920 |
| (General) | C3 - 100 A |
| Catalog page | Page 96 (C-6-2015) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-21/A1 2009 |
| Custom tariff number | 85363030 |
| (Ambient conditions) | IEC 60664-1 |
| Altitude (Dimensions) | max. 2000 m |
| Rated current (General) | 350 mA (45°C) |
| Type (Ambient conditions) | Double-level terminal block with disconnect knife |
| Color (Ambient conditions) | black |
| Depth (Key Commercial Data) | 65.1 mm (incl. DIN rail 7.5 mm) |
| Width (Key Commercial Data) | 6.2 mm |
| Height (Key Commercial Data) | 100 mm |
| Nominal voltage UN (General) | 24 V AC |
| Capacity (line-line) (General) | 2 nF |
| Residual current IPE (General) | ≤ 2 µA |
| Resistance in series (General) | 6.6 Ω ±20 % |
| Capacity (line-earth) (General) | 2 pF |
| VDE requirement class (General) | C1 |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C1 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Input attenuation aE, sym. (General) | typ. 1 dB (400 kHz/50 Ω) |
| Max. required back-up fuse (General) | 370 mA |
| Weight per Piece (excluding packing) | 30.620 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Response time tA(line-line) (General) | ≤ 1 ns |
| Stripping length (Protective circuit) | 8 mm |
| Connection method (Protective circuit) | Spring-cage connection |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Maximum continuous voltage UC (General) | 45 V DC |
| Degree of pollution (Ambient conditions) | 2 |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Impulse durability (line-line) (General) | C2 - 10 kV/5 kA |
| Number of positions (Ambient conditions) | 2 |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | Spring-cage |
| Impulse durability (line-earth) (General) | C2 - 10 kV/5 kA |
| Overvoltage category (Ambient conditions) | III |
| Connection method OUT (Protective circuit) | Spring-cage |
| Standards/specifications (Connection data) | IEC 61643-21/A1 2008 |
| Residual voltage at In(line-line) (General) | ≤ 55 V |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Operating effective current ICat UC (General) | ≤ 10 µA |
| Conductor cross section AWG (Protective circuit) | 24 ... 14 |
| Voltage protection level Up(line-line) (General) | ≤ 80 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(line-earth) (General) | ≤ 600 V (C2 - 10 kV / 5 kA) |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Pulse discharge current Iimp(10/350) µs (General) | 1 kA (per path) |
| Total discharge current Itotal(8/20) µs (General) | 10 kA |
| Total discharge current Itotal(10/350) µs (General) | 2 kA |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Flammability rating according to UL 94 (Ambient conditions) | V-2 |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system (General) | 3.5 MHz |
| Nominal discharge current In(8/20) µs (line-line) (General) | 5 kA |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General) | 1.1 MHz |
| Cut-off frequency fg (3 dB), sym. in 600 Ohm system (General) | typ. 280 kHz |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 5 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) (General) | 100 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) (General) | 200 A (in total) |
| Output voltage limitation at 1 kV/µs (line-line) spike (General) | ≤ 55 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 600 V |
| Output voltage limitation at 1 kV/µs (line-line) static (General) | ≤ 55 V |
| Max. discharge current Imax(8/20) µs maximum (line-line) (General) | 5 kA |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 600 V |
| Standards for cearances and creepage distances (Ambient conditions) | EN 60664-1 |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (General) | 5 kA |
Technical specifications and performance data