Key Specifications
GTIN:4017918101282
Note:Made to Order (non-returnable)
Orderkey:2809607
(General):20 V AC
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918101282
NoteMade to Order (non-returnable)
Orderkey2809607
(General)20 V AC
Catalog pagePage 99 (C-6-2013)
Packing unit50 pc
Country of originDE (Germany)
Custom tariff number85363030
Rated current (General)32 A (50 °C)
Type (Ambient conditions)Single-level terminal block – separate PE connection
Color (Ambient conditions)black
Depth (Key Commercial Data)69.5 mm
Width (Key Commercial Data)6.2 mm
(Standards and Regulations)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Height (Key Commercial Data)66.5 mm
Nominal voltage UN (General)24 V DC
Residual current IPE (General)≤ 5 µA
Capacity (line-earth) (General)1.35 nF
VDE requirement class (General)C3
Degree of protection (Dimensions)IP20
IEC test classification (General)C3
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)DIN rail: 35 mm
Weight per Piece (excluding packing)15.680 g
Housing material (Ambient conditions)PA
Stripping length (Protective circuit)8 mm
China RoHS (Standards and Regulations)Environmentally Friendly Use Period = 50
Connection method (Protective circuit)Screw connection
REACh SVHC (Standards and Regulations)4-Nonylphenol, ethoxylated
Response time tA(line-earth) (General)≤ 1 ns
Tightening torque (Protective circuit)0.5 Nm
Maximum continuous voltage UC (General)28.2 V DC
Standards/regulations (Connection data)IEC 61643-21
Direction of action (Ambient conditions)Line-Earth Ground
Surge protection fault message (General)none
Connection method IN (Protective circuit)Screw terminal blocks
Impulse durability (line-earth) (General)C3 - 25 A
Connection method OUT (Protective circuit)Screw terminal blocks
Ambient temperature (operation) (Dimensions)-40 °C ... 85 °C
Residual voltage at In(line-earth) (General)≤ 59 V
Operating effective current ICat UC (General)≤ 5 µA
Conductor cross section AWG (Protective circuit)24 ... 12
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General)169 A
Conductor cross section flexible (Protective circuit)0.2 mm² ... 4 mm²
Flammability rating according to UL 94 (Ambient conditions)V-2
Nominal discharge current In(8/20) µs (line-earth) (General)169 A
Nominal pulse current Ian (10/1000) µs (line-earth) (General)33 A
Output voltage limitation at 1 kV/µs (line-earth) spike (General)≤ 42 V
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system (General)typ. 1.5 MHz
Output voltage limitation at 1 kV/µs (line-earth) static (General)≤ 41 V
Max. discharge current Imax(8/20) µs maximum (line-earth) (General)169 A

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top