Service time: Monday to Friday 9:00-18:00
TT-SLKK5-S- 12DC - TT-SLKK5-S- 12DC 2809597 PHOENIX CONTACT Surge protection device
In Stock Hot Product

TT-SLKK5-S- 12DC

TT-SLKK5-S- 12DC 2809597 PHOENIX CONTACT Surge protection device

$0.00USD
4653 in stock
Key Specifications
GTIN:4017918101275
Note:Made to Order (non-returnable)
Orderkey:2809597
(General):C3 - 25 A
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918101275
NoteMade to Order (non-returnable)
Orderkey2809597
(General)C3 - 25 A
Catalog pagePage 99 (C-6-2013)
Packing unit50 pc
Country of originDE (Germany)
Custom tariff number85363030
Rated current (General)32 A (50 °C)
Type (Ambient conditions)Single-level terminal block – separate PE connection
Color (Ambient conditions)black
Depth (Key Commercial Data)69.5 mm
Width (Key Commercial Data)6.2 mm
(Standards and Regulations)Lead 7439-92-1
Height (Key Commercial Data)66.5 mm
Nominal voltage UN (General)12 V DC
Residual current IPE (General)≤ 5 µA
Capacity (line-earth) (General)2.35 nF
VDE requirement class (General)C3
Degree of protection (Dimensions)IP20
IEC test classification (General)C1
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)DIN rail: 35 mm
Weight per Piece (excluding packing)19.400 g
Housing material (Ambient conditions)PA
Stripping length (Protective circuit)8 mm
Connection method (Protective circuit)Screw connection
REACh SVHC (Standards and Regulations)4-Nonylphenol, ethoxylated
Response time tA(line-earth) (General)≤ 1 ns
Tightening torque (Protective circuit)0.5 Nm
Maximum continuous voltage UC (General)13.6 V DC
Standards/regulations (Connection data)IEC 61643-21
Direction of action (Ambient conditions)Line-Earth Ground
Surge protection fault message (General)none
Connection method IN (Protective circuit)Screw terminal blocks
Impulse durability (line-earth) (General)C1 - 500 V / 250 A
Connection method OUT (Protective circuit)Screw terminal blocks
Standards/specifications (Connection data)IEC 61643-21 2000
Ambient temperature (operation) (Dimensions)-40 °C ... 85 °C
Residual voltage at In(line-earth) (General)≤ 29 V
Operating effective current ICat UC (General)≤ 5 µA
Conductor cross section AWG (Protective circuit)24 ... 12
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General)346 A
Conductor cross section flexible (Protective circuit)0.2 mm² ... 4 mm²
Flammability rating according to UL 94 (Ambient conditions)V-2
Nominal discharge current In(8/20) µs (line-earth) (General)346 A
Nominal pulse current Ian (10/1000) µs (line-earth) (General)67 A
Output voltage limitation at 1 kV/µs (line-earth) spike (General)≤ 24 V
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system (General)typ. 1 MHz
Output voltage limitation at 1 kV/µs (line-earth) static (General)≤ 19 V
Max. discharge current Imax(8/20) µs maximum (line-earth) (General)346 A

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top