| Parameter | Value |
|---|---|
| GTIN | 4017918066468 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2765602 |
| (General) | 315 mA DC (F) |
| Catalog page | Page 123 (C-6-2013) |
| Packing unit | 50 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-21 2001 |
| Custom tariff number | 85363010 |
| Rated current (General) | 2 A AC |
| Type (Ambient conditions) | Single-level terminal block – separate PE connection |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 69.5 mm |
| Width (Key Commercial Data) | 6.2 mm |
| (Standards and Regulations) | Lead 7439-92-1 |
| Height (Key Commercial Data) | 66.5 mm |
| Nominal voltage UN (General) | 110 V AC |
| Residual current IPE (General) | ≤ 1.5 µA |
| Capacity (line-earth) (General) | typ. 1 pF |
| Degree of protection (Dimensions) | IP20 (with end cover) |
| IEC test classification (General) | C1 |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Max. required back-up fuse (General) | 2 A AC (F) |
| Weight per Piece (excluding packing) | 18.100 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Stripping length (Protective circuit) | 8 mm |
| Connection method (Protective circuit) | Screw connection |
| REACh SVHC (Standards and Regulations) | 4-Nonylphenol, ethoxylated |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Tightening torque (Protective circuit) | 0.8 Nm |
| Maximum continuous voltage UC (General) | 30 V DC |
| Direction of action (Ambient conditions) | Line-Earth Ground |
| Number of positions (Ambient conditions) | 1 |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | Screw terminal blocks |
| Connection method OUT (Protective circuit) | Screw terminal blocks |
| Standards/specifications (Connection data) | IEC 61643-21 2000 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Operating effective current ICat UC (General) | ≤ 2 µA |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Total discharge current Itotal(8/20) µs (General) | 5 kA |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 4 mm² |
| Flammability rating according to UL 94 (Ambient conditions) | V-2 |
| Alternating current carrying capacity (line-earth) (General) | 2.5 A - 1 s |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 5 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 650 V |
| Output voltage limitation at 1 kV/µs (line-earth) static (General) | ≤ 650 V |
| Standards for cearances and creepage distances (Ambient conditions) | VDE 0110-1 |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (General) | 5 kA |
Technical specifications and performance data