Service time: Monday to Friday 9:00-18:00
TT-SLKK5/110AC - TT-SLKK5/110AC 2794987 PHOENIX CONTACT Surge protection device
In Stock Hot Product

TT-SLKK5/110AC

TT-SLKK5/110AC 2794987 PHOENIX CONTACT Surge protection device

$0.00USD
4910 in stock
Key Specifications
GTIN:4017918073053
Orderkey:2794987
(General):C3
Catalog page:Page 69 (TT-2005)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918073053
Orderkey2794987
(General)C3
Catalog pagePage 69 (TT-2005)
Packing unit50 pc
Country of originDE (Germany)
Custom tariff number85363030
Rated current (General)32 A (50 °C)
Type (Ambient conditions)Single-level terminal block – separate PE connection
Color (Ambient conditions)black
Width (Key Commercial Data)6.2 mm
(Standards and Regulations)Lead 7439-92-1
Height (Key Commercial Data)69.5 mm
Length (Key Commercial Data)66.5 mm
Nominal voltage UN (General)110 V AC
Residual current IPE (General)≤ 100 µA
VDE requirement class (General)C1
Degree of protection (Dimensions)IP20
IEC test classification (General)C1
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)DIN rail: 35 mm
Weight per Piece (excluding packing)0.220 g
Housing material (Ambient conditions)PA
Stripping length (Protective circuit)8 mm
Connection method (Protective circuit)Screw connection
REACh SVHC (Standards and Regulations)4-Nonylphenol, ethoxylated
Response time tA(line-earth) (General)≤ 25 ns
Tightening torque (Protective circuit)0.8 Nm
Maximum continuous voltage UC (General)130 V AC
Standards/regulations (Connection data)IEC 61643-21
Direction of action (Ambient conditions)Line-Earth Ground
Number of positions (Ambient conditions)1
Surge protection fault message (General)none
Connection method IN (Protective circuit)Screw terminal blocks
Connection method OUT (Protective circuit)Screw terminal blocks
Ambient temperature (operation) (Dimensions)-40 °C ... 85 °C
Residual voltage at In(line-earth) (General)≤ 500 V
Conductor cross section AWG (Protective circuit)24 ... 12
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General)6.5 kA
Conductor cross section flexible (Protective circuit)0.2 mm² ... 4 mm²
Flammability rating according to UL 94 (Ambient conditions)V-2
Nominal discharge current In(8/20) µs (line-earth) (General)2 kA
Nominal pulse current Ian (10/1000) µs (line-earth) (General)75 A
Output voltage limitation at 1 kV/µs (line-earth) spike (General)≤ 310 V
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system (General)typ. 1.5 MHz
Output voltage limitation at 1 kV/µs (line-earth) static (General)≤ 310 V
Max. discharge current Imax(8/20) µs maximum (line-earth) (General)6.5 kA

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top