| Parameter | Value |
|---|---|
| GTIN | 4017918062316 |
| Orderkey | 2748069 |
| Catalog page | Page 113 (TT-2011) |
| Packing unit | 50 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 60384-14 |
| Custom tariff number | 85363010 |
| Rated current (General) | 30 A (45°C) |
| Type (Ambient conditions) | Single-level terminal block – separate PE connection |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 69.5 mm |
| Width (Key Commercial Data) | 6.2 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 66.5 mm |
| Nominal voltage UN (General) | 230 V AC |
| Residual current IPE (General) | typ. 1.5 mA |
| Capacity (line-earth) (General) | typ. 12 nF |
| Degree of protection (Dimensions) | IP20 (with end cover) |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Weight per Piece (excluding packing) | 21.290 g |
| Housing material (Ambient conditions) | PA |
| Stripping length (Protective circuit) | 8 mm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Connection method (Protective circuit) | Screw connection |
| REACh SVHC (Standards and Regulations) | 4-Nonylphenol, ethoxylated |
| Tightening torque (Protective circuit) | 0.5 Nm |
| Maximum continuous voltage UC (General) | 250 V AC |
| Direction of action (Ambient conditions) | Line-Earth Ground |
| Number of positions (Ambient conditions) | 1 |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | Screw terminal blocks |
| Connection method OUT (Protective circuit) | Screw terminal blocks |
| Standards/specifications (Connection data) | EN 60947-7-1 2009 |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 85 °C |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 4 mm² |
| Flammability rating according to UL 94 (Ambient conditions) | V-2 |
| Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system (General) | typ. 500 kHz |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system (General) | typ. 150 kHz |
| Cut-off frequency fg (3 dB), asym. (PE) in 600 Ohm system (General) | typ. 40 kHz |
Technical specifications and performance data