| Parameter | Value |
|---|---|
| GTIN | 4046356343374 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2805017 |
| (General) | D1 - 500 A |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| (Connection data) | EN 61643-21/A1 2009 |
| Custom tariff number | 85363010 |
| Altitude (Dimensions) | ≤ 2000 m |
| Rated current (General) | 300 mA (40 °C) |
| Type (Ambient conditions) | Double-level terminal block with PE foot – separate PE connection |
| Color (Ambient conditions) | black |
| Depth (Key Commercial Data) | 54.6 mm |
| Width (Key Commercial Data) | 6.2 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 79.6 mm |
| Nominal voltage UN (General) | 12 V DC |
| Capacity (line-line) (General) | ≤ 2.5 nF |
| Residual current IPE (General) | ≤ 1 µA |
| Resistance in series (General) | 3.7 Ω 5 % |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C1 |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Input attenuation aE, sym. (General) | typ. 0.6 dB (≤ 400 kHz/50 Ω) |
| Max. required back-up fuse (General) | 315 mA (T/IEC 60127-2/3) |
| Weight per Piece (excluding packing) | 26.600 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Response time tA(line-line) (General) | ≤ 1 ns |
| Stripping length (Protective circuit) | 8 mm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Connection method (Protective circuit) | Screw connection |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Response time tA(line-earth) (General) | ≤ 100 ns |
| Tightening torque (Protective circuit) | 0.6 Nm |
| Maximum continuous voltage UC (General) | 18 V DC |
| Direction of action (Ambient conditions) | Line-Line & Line-Earth Ground |
| Impulse durability (line-line) (General) | C1 - 1 kV/500 A |
| Number of positions (Ambient conditions) | 2 |
| Surge protection fault message (General) | none |
| Connection method IN (Protective circuit) | Screw terminal blocks |
| Impulse durability (line-earth) (General) | C1 - 1 kV/500 A |
| Connection method OUT (Protective circuit) | Screw terminal blocks |
| Standards/specifications (Connection data) | IEC 61643-21/A1 2008 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Operating effective current ICat UC (General) | ≤ 10 µA |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Voltage protection level Up(line-line) (General) | ≤ 55 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(line-earth) (General) | ≤ 850 V (C2 - 10 kV / 5 kA) |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Pulse discharge current Iimp(10/350) µs (General) | 500 A |
| Total discharge current Itotal(8/20) µs (General) | 10 kA |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Alternating current carrying capacity (line-line) (General) | 0.5 A - 1 s |
| Flammability rating according to UL 94 (Ambient conditions) | V-2 |
| Alternating current carrying capacity (line-earth) (General) | 1 A/1s |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system (General) | typ. 2.5 MHz |
| Nominal discharge current In(8/20) µs (line-line) (General) | 5 kA |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General) | typ. 800 kHz |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 5 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) (General) | 100 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) (General) | 100 A |
| Output voltage limitation at 1 kV/µs (line-line) spike (General) | ≤ 30 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike (General) | ≤ 650 V |
| Standards for cearances and creepage distances (Ambient conditions) | IEC 60664-1 |
Technical specifications and performance data
Installation and operation guide