| Parameter | Value |
|---|---|
| 65 V DC | |
| Fuse | Slow-blow |
| Type | Male |
| Depth | 44.5 mm |
| Width | 8.2 mm |
| Height | 24.4 mm |
| General | When mounted in rows, the nominal device current can be limited to just 80% or must be overdimensioned accordingly. |
| Altitude | ≤ 4000 m (amsl) |
| Fuse type | Automatic device |
| Product type | Thermal device circuit breakers |
| Humidity test | 240 h, 95 % RH, 40 °C |
| Mounting type | on base element |
| Rated voltage | 250 V AC |
| Open side panel | No |
| Tripping method | T (thermal) |
| Rated current IN | 5 A |
| Connection method | pluggable |
| Device resistance | 0.05 Ω |
| Degree of pollution | 2 |
| Dielectric strength | 3000 V AC (Actuation area) |
| Dimensional drawing | |
| Insulating material | PPS |
| Number of positions | 1 |
| Rated surge voltage | 2.5 kV |
| Degree of protection | IP40 (Actuation area) |
| Overvoltage category | II |
| Switching cycles, max. | 6000 (At 1 x In, low-induction) |
| Insulating material group | IIIb |
| Insulation resistance Riso | > 100 MΩ (500 V DC) |
| Ambient temperature (operation) | -20 °C ... 60 °C |
| Short-circuit switching capacity | 2000 A (250 V AC / UL 1077) |
| Flammability rating according to UL 94 | V-0 |
| Rated short-circuit switching capacity Icn | 30 A (250 V AC / 65 V DC) |
| Maximum power dissipation for nominal condition | ≤ 0.9 VA |
Technical specifications and performance data
Installation and operation guide