| Parameter | Value |
|---|---|
| When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules. | |
| Fuse | electronic |
| Note | LABS release – in accordance with test specification VW PV 3.10.7:2005-0 |
| Depth | 111.3 mm (incl. DIN rail 7.5 mm) |
| Width | 12.4 mm |
| Height | 132.4 mm |
| Altitude | ≤ 4000 m (amsl) |
| Material | PA 6 |
| Efficiency | > 99 % |
| Product type | Device circuit breakers |
| Voltage drop | 0.06 V (at 4 A) |
| Humidity test | 96 h, 95 % RH, 40 °C |
| Mounting type | pluggable onto CAPAROC CR… current rail |
| Rated voltage | 12 V DC |
| Shutdown time | 5 s (with overload 1.1…1.3 x INat IN≥ 4 A) |
| Identification | UL/C-UL Listed UL 508 |
| Product family | CAPAROC |
| Channel LED off | off (Channel switched off) |
| Channel LED red | lit (Channel switched off, over- or undervoltage active) |
| No. of channels | 2 |
| Number of slots | 2 |
| Switch-on delay | 50 ms (each channel preset by default) |
| Tripping method | E (electronic) |
| Pollution degree | 2 |
| Protection class | III |
| Rated current IN | 4 A DC (per channel) |
| Stripping length | 10 mm |
| Channel LED green | lit (Channel switched on) |
| Connection method | Push-in connection |
| Cross section AWG | (converted acc. to IEC) |
| Fail-safe element | 5 A DC (per output channel) |
| Operating voltage | 10 V DC ... 30 V DC |
| Power dissipation | typ. 0.6 W (no load at 24 V) |
| Shock (operation) | 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27) |
| Channel LED yellow | lit (Channel switched on, channel load > 80% ) |
| Dielectric strength | 35 V DC (Load circuit) |
| Dimensional drawing | |
| Feedback resistance | max. 35 V DC |
| Number of positions | 1 |
| Rated surge voltage | 0.5 kV |
| Degree of protection | IP20 |
| Max. capacitive load | ≤ 60000 µF (Depending on the current setting and the short-circuit current available) |
| Required backup fuse | Only required if Imaxof the power supply > the short-circuit switching capacity. Integrated failsafe element. |
| Channel LED red-green | flashing (Channel switched off, programming mode active, current adjustment after overload or short-circuit release) |
| Measuring tolerance I | ± 10 % (typ.) |
| Vibration (operation) | 5g (10 ... 150 Hz / 10 cycles / axis / X, Y, Z) |
| Channel LED red-yellow | flashing (Channel is overloaded and is switched off) |
| Overvoltage switch-off | ≥ 32.5 V DC (active) |
| Undervoltage switch-off | ≤ 8.5 V DC (active) |
| Standards/specifications | EN 61000-6-2 |
| Active current limitation | typ. 2.0 x INat IN≤ 3 A |
| Closed circuit current I0 | typ. 25 mA (no load at 24 V) |
| MTBF (IEC 61709, SN 29500) | 11364927 h (at 25 °C with 21 % load) |
| Conductor cross section AWG | 24 ... 12 |
| Rated current (pre-adjusted) | 1 A |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Ambient temperature (operation) | -30 °C ... 65 °C (The temperature range of the power module must be taken into consideration) |
| Conductor cross section flexible | 0.2 mm² ... 4 mm² |
| Short-circuit switching capacity | 300 A |
| Flammability rating according to UL 94 | V-0 |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 4 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 4 mm² |
Technical specifications and performance data
Installation and operation guide