Service time: Monday to Friday 9:00-18:00
CAPAROC E2 12-24DC/2-10A EX - CAPAROC E2 12-24DC/2-10A EX 1344364 PHOENIX CONTACT 2-channel electronic switch module for equipment protect..
In Stock Hot Product

CAPAROC E2 12-24DC/2-10A EX

CAPAROC E2 12-24DC/2-10A EX 1344364 PHOENIX CONTACT 2-channel electronic switch module for equipment protect..

$107.87USD
125 in stock
Key Specifications
:When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules.
Fuse:electronic
Note:LABS release – in accordance with test specification VW PV 3.10.7:2005-0
Type:Plug-in module
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules.
Fuseelectronic
NoteLABS release – in accordance with test specification VW PV 3.10.7:2005-0
TypePlug-in module
Depth111.3 mm (incl. DIN rail 7.5 mm)
Width12.4 mm
Height132.4 mm
Altitude≤ 4000 m (amsl)
MaterialPA 6
Efficiency> 99 %
Product typeDevice circuit breakers
Voltage drop0.14 V (at 10 A)
Humidity test96 h, 95 % RH, 40 °C
Mounting typepluggable onto CAPAROC CR… current rail
Rated voltage12 V DC
Shutdown time5 s (for overload 1.1…1.3 x INat IN≥ 4 A)
IdentificationUL/C-UL Listed UL 508
Product familyCAPAROC
Channel LED offoff (Channel switched off)
Channel LED redlit (Channel switched off, over- or undervoltage active)
No. of channels2
Number of slots2
Switch-on delay50 ms (each channel preset by default)
Tripping methodE (electronic)
Pollution degree2
Protection classIII
Rated current IN10 A DC (per channel)
Stripping length10 mm
Channel LED greenlit (Channel switched on)
Connection methodPush-in connection
Cross section AWG(converted acc. to IEC)
Fail-safe element15 A DC (per output channel)
Operating voltage10 V DC ... 30 V DC
Power dissipationtyp. 0.6 W (no load at 24 V)
Shock (operation)30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27)
Channel LED yellowlit (Channel switched on, channel load > 80% )
Dielectric strength35 V DC (Load circuit)
Dimensional drawing
Feedback resistancemax. 35 V DC
Number of positions1
Rated surge voltage0.5 kV
Degree of protectionIP20
Max. capacitive load≤ 75000 µF (Depending on the current setting and the short-circuit current available)
Required backup fuseOnly required if Imaxof the power supply > the short-circuit switching capacity. Integrated failsafe element.
Temperature derating20 A (Total current at 40°C)
Channel LED red-greenflashing (Channel switched off, programming mode active, current adjustment after overload or short-circuit release)
Measuring tolerance I± 10 % (typ.)
Vibration (operation)5g (10 ... 150 Hz / 10 cycles / axis / X, Y, Z)
Channel LED red-yellowflashing (Channel is overloaded and is switched off)
Overvoltage switch-off≥ 32.5 V DC (active)
Undervoltage switch-off≤ 8.5 V DC (active)
Standards/specificationsEN 61000-6-2
Active current limitationtyp. 2.0 x INat IN≤ 3 A
Closed circuit current I0typ. 25 mA (no load at 24 V)
MTBF (IEC 61709, SN 29500)11140621 h (at 25 °C with 21 % load)
Conductor cross section AWG24 ... 12
Rated current (pre-adjusted)2 A
Conductor cross section rigid0.2 mm² ... 4 mm²
Ambient temperature (operation)-30 °C ... 65 °C (The temperature range of the power module must be taken into consideration)
Conductor cross section flexible0.2 mm² ... 4 mm²
Short-circuit switching capacity300 A
Flammability rating according to UL 94V-0
Ambient temperature (storage/transport)-40 °C ... 70 °C
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 4 mm²
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 4 mm²

Product Description

Electronic Appliance Protection Switches
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide