| Parameter | Value |
|---|---|
| III (Actuation area) | |
| Fuse | Slow-blow |
| Type | Male |
| Depth | 44.5 mm |
| Width | 9.5 mm |
| Height | 24.4 mm |
| Altitude | ≤ 4000 m (amsl) |
| Fuse type | Automatic device |
| Product type | Thermal device circuit breakers |
| Humidity test | 240 h, 95 % RH, 40 °C |
| Mounting type | on base element |
| Rated voltage | 250 V AC |
| Open side panel | No |
| Tripping method | T (thermal) |
| Rated current IN | 12 A |
| Connection method | pluggable |
| Device resistance | 0 Ω |
| Shock (operation) | 25g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27) |
| Degree of pollution | 2 |
| Dielectric strength | 3000 V AC (Actuation area) |
| Dimensional drawing | |
| Insulating material | PPS |
| Number of positions | 1 |
| Rated surge voltage | 2.5 kV |
| Degree of protection | IP40 (Actuation area) |
| Overvoltage category | II |
| Vibration (operation) | ± 0.38 mm (10 ... 57 Hz) |
| Switching cycles, max. | 6000 (At 1 x In, low-induction) |
| Insulating material group | IIIb |
| Insulation resistance Riso | > 100 MΩ (500 V DC) |
| Ambient temperature (operation) | -20 °C ... 60 °C |
| Short-circuit switching capacity | 2000 A (250 V AC / UL 1077) |
| Flammability rating according to UL 94 | V-0 |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Rated short-circuit switching capacity Icn | 30 A (250 V AC) |
Technical specifications and performance data