| Parameter | Value |
|---|---|
| GTIN | 4046356158565 |
| Orderkey | 2920683 |
| (General) | 1 kA AC (IT) |
| Catalog page | Page 185 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| (Connection data) | N-G |
| Custom tariff number | 85363010 |
| (Ambient conditions) | silver |
| (Protective circuit) | 1 A DC (48 V DC) |
| Capacity (L-N) (General) | 1 µF ±10 % |
| Capacity (L-PE) (General) | 2.2 nF ±20 % (Y2-250 V) |
| Type (Ambient conditions) | DIN rail module, one-piece |
| Capacity (L-PEN) (General) | 2.2 nF ±20 % (Y2-250 V) |
| Color (Ambient conditions) | black |
| Response time tA (General) | ≤ 25 ns |
| SPD Type (Connection data) | 2CA |
| Depth (Key Commercial Data) | 79 mm |
| Width (Key Commercial Data) | 112 mm |
| EN type (Ambient conditions) | T3 |
| Height (Key Commercial Data) | 86.6 mm |
| Nominal voltage UN (General) | 120 V AC (TN) |
| (Indicator/remote signaling) | 4.5 lbf-in. ... 5.5 lbf-in. |
| Combination wave UOC (General) | 6 kV (3 kA) |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 0.6 mA |
| Rated load current IL (General) | 15 A (50 °C) |
| Degree of protection (Dimensions) | IP20 |
| Screw thread (Protective circuit) | M2 |
| TOV behavior at UT(L-N) (General) | 175 V AC (5 s / withstand mode) |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| TOV behavior at UT(L-PE) (General) | 208 V AC (5 s / withstand mode) |
| TOV behavior at UT(N-PE) (General) | 1200 V AC (200 ms / safe failure mode) |
| Nominal frequency (Connection data) | 50/60 Hz |
| Input attenuation aE, sym. (General) | 20 dB (≥ 100 kHz / 50 Ω) |
| Max. required back-up fuse (General) | 20 A (MCB B/general purpose) |
| Mode of protection (Connection data) | L-N |
| Number of ports (Ambient conditions) | Two |
| Weight per Piece (excluding packing) | 571.280 g |
| Housing material (Ambient conditions) | Aluminum |
| Input attenuation aE, asym. (General) | 30 dB (≥ 1 MHz / 50 Ω) |
| Reference test voltage UREF (General) | 132 V AC |
| Stripping length (Protective circuit) | 7 mm |
| Voltage protection level Up (General) | ≤ 0.45 kV |
| Connection method (Protective circuit) | Pluggable screw connection |
| Operating current (Protective circuit) | 100 mA AC ... 1 A AC |
| Operating voltage (Protective circuit) | 12 V AC ... 250 V AC |
| Standby power consumption PC (General) | ≤ 7.5 VA (at UREF) |
| Tightening torque (Protective circuit) | 0.25 Nm |
| Maximum continuous voltage UC (General) | 150 V AC |
| Mode of protection (Ambient conditions) | L-N |
| Switching function (Protective circuit) | PDT contact |
| Degree of pollution (Ambient conditions) | 2 |
| Discharge resistance (UL specifications) | 820 kΩ |
| Number of positions (Ambient conditions) | 2 |
| Screw thread (Indicator/remote signaling) | M3 |
| Power distribution system (Connection data) | Single phase |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C |
| Short-circuit current rating ISCCR (General) | 5 kA AC (TN/TT) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Stripping length (Indicator/remote signaling) | 8 mm |
| Connection method (Indicator/remote signaling) | Screw terminal blocks |
| Nominal discharge current In (Connection data) | 3 kA |
| Tightening torque (Indicator/remote signaling) | 0.5 Nm ... 0.6 Nm |
| Conductor cross section AWG (Protective circuit) | 26 ... 16 |
| For country-specific use in (Ambient conditions) | USA, CN, BR |
| Nominal discharge current In(8/20) µs (General) | 3 kA |
| Conductor cross section solid (Protective circuit) | 0.14 mm² ... 1.5 mm² |
| Surge protection fault message (Ambient conditions) | Optical, remote indicator contact |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 70 °C |
| Conductor cross section flexible (Protective circuit) | 0.14 mm² ... 1.5 mm² |
| Short-circuit current rating (SCCR) (Connection data) | 5 kA |
| Voltage protection rating VPR (L-G) (Connection data) | 500 V |
| Voltage protection rating VPR (L-N) (Connection data) | 500 V |
| Voltage protection rating VPR (N-G) (Connection data) | 500 V |
| Conductor cross section AWG (Indicator/remote signaling) | 14 ... 10 |
| Conductor cross section solid (Indicator/remote signaling) | 2.5 mm² ... 6 mm² |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Conductor cross section flexible (Indicator/remote signaling) | 2.5 mm² ... 4 mm² |
| Maximum continuous operating voltage MCOV (L-G) (Connection data) | 150 V AC |
| Maximum continuous operating voltage MCOV (L-N) (Connection data) | 150 V AC |
| Maximum continuous operating voltage MCOV (N-G) (Connection data) | 150 V AC |
Technical specifications and performance data
Installation and operation guide