Key Specifications
GTIN:4046356091657
Note:Made to Order (non-returnable)
Orderkey:2882569
(General):D1 - 1 kA
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356091657
NoteMade to Order (non-returnable)
Orderkey2882569
(General)D1 - 1 kA
Catalog pagePage 101 (C-4-2017)
Packing unit1 pc
Country of originDE (Germany)
Custom tariff number85369010
(Ambient conditions)VDE 0110-1
Altitude (Dimensions)≤ 2000 m (amsl (above mean sea level))
Rated current (General)450 mA (55 °C)
Type (Ambient conditions)Screw-in module
Color (Ambient conditions)silver
Depth (Key Commercial Data)148 mm
Width (Key Commercial Data)33.5 mm
Height (Key Commercial Data)33.5 mm
Nominal voltage UN (General)24 V DC
Residual current IPE (General)≤ 2 µA
Resistance in series (General)2.2 Ω ±10 %
Degree of protection (Dimensions)IP67
IEC test classification (General)C1
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)direct screw connection
Input attenuation aE, sym. (General)typ. 0.5 dB (≤ 1.5 MHz / 50 Ω)
Max. required back-up fuse (General)500 mA (T)
Weight per Piece (excluding packing)363.840 g
Housing material (Ambient conditions)Zinc die-cast, surface bronzed and nickel-plated
Response time tA(line-line) (General)≤ 1 ns
Stripping length (Protective circuit)6 mm
Connection method (Protective circuit)Screw connection
Response time tA(line-earth) (General)≤ 100 ns
Tightening torque (Protective circuit)0.6 Nm
Maximum continuous voltage UC (General)40 V DC
Direction of action (Ambient conditions)Line-Line & Line-Earth Ground
Impulse durability (line-line) (General)C2 - 10 kV/5 kA
Number of positions (Ambient conditions)3
Surge protection fault message (General)none
Connection method IN (Protective circuit)Screw terminal blocks
Impulse durability (line-earth) (General)C2 - 10 kV/5 kA
Response time tA (shield-earth) (General)≤ 100 ns
Connection method OUT (Protective circuit)Connection line
Connection technology (Protective circuit)Screw connection
Standards/specifications (Connection data)IEC 61643-21 2002
Impulse durability (shield-earth) (General)C2 - 10 kV / 5 kA
Residual voltage at In(line-line) (General)≤ 55 V
Ambient temperature (operation) (Dimensions)-40 °C ... 85 °C
Operating effective current ICat UC (General)≤ 10 µA
Conductor cross section AWG (Protective circuit)26 ... 16
Voltage protection level Up(line-line) (General)≤ 80 V (C2 - 10 kV / 5 kA)
Voltage protection level Up(line-earth) (General)≤ 450 V (C2 - 10 kV / 5 kA)
Conductor cross section solid (Protective circuit)0.14 mm² ... 1.5 mm²
Pulse discharge current Iimp(10/350) µs (General)1 kA
Total discharge current Itotal(8/20) µs (General)20 kA
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 85 °C
Total discharge current Itotal(10/350) µs (General)2 kA
Voltage protection level Up(shield-ground) (General)≤ 600 V (C2 - 10 kV / 5 kA)
Conductor cross section flexible (Protective circuit)0.14 mm² ... 1.5 mm²
Voltage protection level Upstatic (line-line) (General)≤ 50 V (C2 - 10 kV / 5 kA)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system (General)typ. 6 MHz
Nominal discharge current In(8/20) µs (line-line) (General)10 kA
Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General)typ. 2 MHz
Nominal discharge current In(8/20) µs (line-earth) (General)10 kA (per path)
Nominal pulse current Ian (10/1000) µs (line-line) (General)23 A
Residual voltage with Ian (10/1000) µs (line-line) (General)≤ 65 V
Nominal pulse current Ian (10/1000) µs (line-earth) (General)100 A
Nominal discharge current In(8/20) µs (shield-earth) (General)10 kA (optional)
Nominal pulse current Ian (10/1000) µs (Shield-Earth) (General)100 A
Output voltage limitation at 1 kV/µs (line-line) spike (General)≤ 55 V
Output voltage limitation at 1 kV/µs (line-earth) spike (General)≤ 450 V (Direct grounding)
Output voltage limitation at 1 kV/µs (line-line) static (General)≤ 55 V
Max. discharge current Imax(8/20) µs maximum (line-line) (General)10 kA
Output voltage limitation at 1 kV/µs (line-earth) static (General)≤ 450 V (Direct grounding)
Standards for cearances and creepage distances (Ambient conditions)IEC 60664-1
Max. discharge current Imax(8/20) µs maximum (line-earth) (General)10 kA (per path)
Output voltage limitation at 1 kV/µs (shield-earth) spike (General)≤ 600 V (optional)
Max. discharge current Imax(8/20) µs maximum (shield-earth) (General)10 kA

Product Description

Overvoltage protection. in IP67 screw-on module for measuring probes, direct mounting via 1/2'' NPT ext. thread, cable gland for signal line, protective circuit. two levels. Suitable for HAR
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top