

| Parameter | Value |
|---|---|
| Connection for signal line tested in accordance with EN 61000-4-4 with 1 kV; if necessary, customer must provide appropriate protective measures | |
| EMC | B |
| Fuse | electronic |
| Note | EN 50121-3-2: Railway applications - Electromagnetic compatibility - Part 3-2: Rolling stock – Apparatus |
| Type | DIN rail module, one-piece |
| Depth | 55.6 mm (incl. DIN rail 7.5 mm) |
| Width | 6.2 mm |
| Height | 105.8 mm |
| Altitude | ≤ 3000 m up to 52 °C (amsl) |
| Humidity | B |
| Material | PBT |
| Enclosure | A |
| Vibration | B |
| Efficiency | > 99 % |
| Temperature | A |
| Product type | Device circuit breakers |
| Voltage drop | 0.13 V (at 8 A) |
| Humidity test | 96 h, 95 % RH, 40 °C |
| Mounting type | DIN rail: 35 mm |
| Rated voltage | 24 V DC |
| Shutdown time | ≤ 10 ms (for short circuit > 2.0 x IN) |
| Identification | UL/C-UL Listed UL 508 |
| Product family | PTCB |
| Channel LED off | off (Channel switched off) |
| Channel LED red | lit (Channel switched off, over- or undervoltage active) |
| Connection name | Remote indication circuit |
| Tripping method | E (electronic) |
| Pollution degree | 2 |
| Protection class | III |
| Rated current IN | 24 A DC (Total current input) |
| Stripping length | 8 mm |
| Channel LED green | lit (Channel switched on) |
| Connection method | Push-in connection |
| Cross section AWG | (converted acc. to IEC) |
| Fail-safe element | 15 A DC |
| Operating current | 100 mA DC |
| Operating voltage | 18 V DC ... 30 V DC |
| Power dissipation | typ. 0.3 W (No-load operation) |
| Shock (operation) | 30g (IEC 60068-2-27, Test Ea) |
| Channel LED yellow | lit (Channel switched on, channel load > 80% ) |
| Switching function | N/O contact |
| Dielectric strength | max. 35 V DC (Load circuit) |
| Dimensional drawing | |
| Feedback resistance | max. 35 V DC |
| Number of positions | 1 |
| Rated surge voltage | 0.5 kV |
| Degree of protection | IP20 |
| Max. capacitive load | 25000 µF (Depending on the current setting and the short-circuit current available) |
| Required backup fuse | Only required if Imaxof the power supply > the short-circuit switching capacity. Integrated failsafe element. |
| Temperature derating | 21 A (Total current at 60°C) |
| Measuring tolerance I | ± 15 % |
| Vibration (operation) | 10 Hz ... 59.6 Hz (Amplitude ±0.35 mm; in accordance with IEC 60068-2-6, Test Fc) |
| Overvoltage switch-off | ≥ 30.5 V DC (active) |
| Undervoltage switch-off | ≤ 17.8 V DC (active) |
| Standards/specifications | EN 61000-6-2 |
| Closed circuit current I0 | typ. 12 mA |
| MTBF (IEC 61709, SN 29500) | 25641025 h (at 25 °C with 21 % load) |
| Module initialization time | < 0.55 s |
| Conductor cross section AWG | 24 ... 12 |
| Rated current (pre-adjusted) | 4 A |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Ambient temperature (operation) | -30 °C ... 60 °C |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Short-circuit switching capacity | 300 A |
| Flammability rating according to UL 94 | V-0 |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Waiting time after switch off of a channel | 5 s (at overload / short circuit) |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
Technical specifications and performance data
Installation and operation guide