| Parameter | Value |
|---|---|
| GTIN | 4017918819323 |
| Orderkey | 2819008 |
| (General) | 44 V DC |
| Catalog page | Page 99 (C-4-2017) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| EN type (General) | T3 |
| Custom tariff number | 85363010 |
| (Power supply, general) | D1 |
| Type (Ambient conditions) | Male |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 51.7 mm |
| Width (Key Commercial Data) | 17.5 mm |
| Height (Key Commercial Data) | 44.8 mm |
| Response time (L-N) (General) | ≤ 25 ns |
| Combination wave UOC (General) | 2 kV |
| Nominal frequency fN (General) | 50 Hz (60 Hz) |
| Residual current IPE (General) | ≤ 5 µA |
| Response time (L-PE) (General) | ≤ 100 ns |
| Rated load current IL (General) | 6 A (30 °C) |
| Mounting type (Ambient conditions) | on base element |
| Arrester rated voltage UC (General) | 34 V AC |
| Weight per Piece (excluding packing) | 25.830 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Direction of action (Ambient conditions) | L-N-PE & Signal Line-Signal Line-Earth Ground |
| Surge protection fault message (General) | optical |
| Voltage protection level Up(L-N) (General) | ≤ 0.18 kV |
| Complete module depth (Key Commercial Data) | 65.5 mm |
| Complete module width (Key Commercial Data) | 17.7 mm |
| Voltage protection level Up(L-PE) (General) | ≤ 0.55 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Complete module height (Key Commercial Data) | 90 mm |
| Operating effective current ICat UC (General) | ≤ 1.5 mA |
| IEC test classification (Power supply, general) | C1 |
| Max. discharge current Imax(8/20) µs (General) | 2 kA |
| Screw thread (Protective circuit, power supply) | M3 |
| (Connection (protective circuit, power supply)) | D1 - 2.5 kA |
| Nominal discharge current In(8/20) µs (General) | 700 A |
| Stripping length (Protective circuit, power supply) | 8 mm |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Connection method (Protective circuit, power supply) | Screw connection (in connection with the base element) |
| Connection method IN (Protective circuit, power supply) | PLUGTRAB plug-in system |
| Connection method OUT (Protective circuit, power supply) | PLUGTRAB plug-in system |
| Screw thread (Protective circuit, information technology) | M3 |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Rated current (Connection (protective circuit, power supply)) | 450 mA (45°C) |
| Stripping length (Protective circuit, information technology) | 8 mm |
| Connection method (Protective circuit, information technology) | Screw connection (in connection with the base element) |
| Connection method IN (Protective circuit, information technology) | PLUGTRAB plug-in system |
| Connection method OUT (Protective circuit, information technology) | PLUGTRAB plug-in system |
| Nominal voltage UN (Connection (protective circuit, power supply)) | 24 V AC |
| Capacity (line-line) (Connection (protective circuit, power supply)) | typ. 1.1 nF |
| Residual current IPE (Connection (protective circuit, power supply)) | ≤ 2 µA |
| Resistance in series (Connection (protective circuit, power supply)) | 2.2 Ω ±10 % |
| Capacity (line-earth) (Connection (protective circuit, power supply)) | typ. 4 pF |
| Arrester rated voltage UC (Connection (protective circuit, power supply)) | 40 V DC |
| Input attenuation aE, sym. (Connection (protective circuit, power supply)) | typ. 0.5 dB (≤ 1.5 MHz / 50 Ω) |
| Response time tA(line-line) (Connection (protective circuit, power supply)) | ≤ 1 ns |
| Response time tA(line-earth) (Connection (protective circuit, power supply)) | ≤ 100 ns |
| Impulse durability (line-line) (Connection (protective circuit, power supply)) | C2 - 10 kV/5 kA |
| Surge protection fault message (Connection (protective circuit, power supply)) | Optical, remote indicator contact |
| Impulse durability (line-earth) (Connection (protective circuit, power supply)) | C2 - 10 kV/5 kA |
| Residual voltage at In(line-line) (Connection (protective circuit, power supply)) | ≤ 55 V |
| Operating effective current ICat UC (Connection (protective circuit, power supply)) | ≤ 5 µA |
| Voltage protection level Up(line-line) (Connection (protective circuit, power supply)) | ≤ 80 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(line-earth) (Connection (protective circuit, power supply)) | ≤ 450 V (C2 - 10 kV / 5 kA) |
| Output voltage limitation at 1 kV/µs (wire-wire) (Connection (protective circuit, power supply)) | ≤ 55 V |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system (Connection (protective circuit, power supply)) | typ. 8 MHz |
| Nominal discharge current In(8/20) µs (line-line) (Connection (protective circuit, power supply)) | 10 kA |
| Output voltage limitation at 1 kV/µs (wire-earth) (Connection (protective circuit, power supply)) | ≤ 25 V |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system (Connection (protective circuit, power supply)) | typ. 3 MHz |
| Cut-off frequency fg (3 dB), sym. in 600 Ohm system (Connection (protective circuit, power supply)) | typ. 800 kHz |
| Nominal discharge current In(8/20) µs (line-earth) (Connection (protective circuit, power supply)) | 10 kA |
| Residual voltage with Ian (10/1000) µs (line-line) (Connection (protective circuit, power supply)) | ≤ 65 V |
| Max. discharge current Imax(8/20) µs maximum (line-line) (Connection (protective circuit, power supply)) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) (Connection (protective circuit, power supply)) | 20 kA (in total) |
| Current supply arrester can be tested with CHECKMASTER starting with software version: (Ambient conditions) | From SW rev. 1.00 |
Technical specifications and performance data