Service time: Monday to Friday 9:00-18:00
PT-IQ-5-HF-5DC-UT - PT-IQ-5-HF-5DC-UT 2800797 PHOENIX CONTACT Surge protection device
In Stock Hot Product

PT-IQ-5-HF-5DC-UT

PT-IQ-5-HF-5DC-UT 2800797 PHOENIX CONTACT Surge protection device

$0.00USD
4589 in stock
Key Specifications
GTIN:4046356665193
Note:Made to Order (non-returnable)
Orderkey:2800797
(General):C3 - 50 A
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356665193
NoteMade to Order (non-returnable)
Orderkey2800797
(General)C3 - 50 A
Catalog pagePage 146 (C-4-2017)
Packing unit1 pc
Country of originDE (Germany)
Custom tariff number85363010
Altitude (Dimensions)≤ 4000 m (amsl (above mean sea level))
Rated current (General)600 mA (40 °C)
Type (Ambient conditions)DIN rail module, two-section, divisible
Color (Ambient conditions)jet black RAL 9005
Depth (Key Commercial Data)77.5 mm (incl. DIN rail 7.5 mm)
Width (Key Commercial Data)17.7 mm
Height (Key Commercial Data)91 mm
Nominal voltage UN (General)5 V DC
Capacity (line-line) (General)typ. 30 pF
Residual current IPE (General)≤ 800 µA (per path)
Resistance in series (General)1.2 Ω ±5 %
Degree of protection (Dimensions)IP20
IEC test classification (General)C1
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)DIN rail: 35 mm
Connection method (Connection data)DIN rail NS35
(Connection, equipotential bonding)EN 61000-6-3 2007 + A1:2011
Input attenuation aE, sym. (General)typ. 0.3 dB (≤ 10 MHz/150 Ω)
Max. required back-up fuse (General)600 mA (FF)
Weight per Piece (excluding packing)146.500 g
Housing material (Ambient conditions)PA 6.6
Input attenuation aE, asym. (General)typ. 0.3 dB (≤ 10 MHz/150 Ω)
Response time tA(line-line) (General)≤ 1 ns
Stripping length (Protective circuit)8 mm
Capacity (line-signalground) (General)typ. 30 pF
Connection method (Protective circuit)Screw connection
Horizontal pitch (Key Commercial Data)1 Div.
Pulse reset time (line-line) (General)≤ 10 ms
Response time tA(line-earth) (General)≤ 1 ns
Tightening torque (Protective circuit)0.5 Nm
Maximum continuous voltage UC (General)6 V DC
Pulse reset time (line-earth) (General)≤ 10 ms
Transmission speed (Ambient conditions)90 Mpbs
Direction of action (Ambient conditions)Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Impulse durability (line-line) (General)C1 - 1 kV/500 A
Surge protection fault message (General)Optical, multi-stage
Impulse durability (line-earth) (General)C1 - 1 kV/500 A
Ambient temperature (operation) (Dimensions)-40 °C ... 70 °C
Operating effective current ICat UC (General)≤ 800 µA (per path)
Conductor cross section AWG (Protective circuit)24 ... 12
Impulse durability (line-signalground) (General)C1 - 1 kV/500 A
Voltage protection level Up(line-line) (General)≤ 90 V (C1 - 1 kV/500 A)
Voltage protection level Up(line-earth) (General)≤ 90 V (C1 - 1 kV/500 A)
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General)20 kA
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 85 °C
Conductor cross section flexible (Protective circuit)0.2 mm² ... 2.5 mm²
Voltage protection level Upstatic (line-line) (General)≤ 45 V (C1 - 1 kV/500 A)
Voltage protection level Upstatic (line-earth) (General)≤ 45 V (C1 - 1 kV/500 A)
Flammability rating according to UL 94 (Ambient conditions)V-0
Nominal discharge current In(8/20) µs (line-line) (General)10 kA
Standards/specifications (Connection, equipotential bonding)IEC 61643-21 2000 + A1:2008 + A2:2012
Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General)typ. 60 MHz
Nominal discharge current In(8/20) µs (line-earth) (General)10 kA
Pulse discharge current Iimp(10/350) µs (line-earth) (General)2.5 kA
Standards for cearances and creepage distances (Ambient conditions)IEC 60664-1
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system (General)typ. 60 MHz

Product Description

Surge protection, consisting of plug-in protection and base element, with multi-level diagnostic and status indication integrated into a module for five signal conductors. For HF applications and tele
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top