| Parameter | Value |
|---|---|
| GTIN | 4046356766692 |
| Orderkey | 2801288 |
| (General) | D1 - 2.5 kA |
| Catalog page | Page 153 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85363010 |
| Altitude (Dimensions) | ≤ 4000 m (amsl (above mean sea level)) |
| Rated current (General) | 600 mA (40 °C) |
| Type (Ambient conditions) | DIN rail module, two-section, divisible |
| Color (Ambient conditions) | jet black RAL 9005 |
| Depth (Key Commercial Data) | 77.5 mm (incl. DIN rail 7.5 mm) |
| Width (Key Commercial Data) | 17.7 mm |
| Height (Key Commercial Data) | 109.3 mm |
| Nominal voltage UN (General) | 12 V DC |
| Capacity (line-line) (General) | typ. 30 pF |
| Residual current IPE (General) | ≤ 100 µA (per path) |
| Resistance in series (General) | 1.2 Ω ±5 % |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | C1 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Connection method (Connection data) | DIN rail NS35 |
| (Connection, equipotential bonding) | EN 61000-6-3 2007 + A1:2011 |
| Input attenuation aE, sym. (General) | typ. 0.3 dB (≤ 10 MHz/150 Ω) |
| Max. required back-up fuse (General) | 600 mA (FF) |
| Weight per Piece (excluding packing) | 109.000 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Input attenuation aE, asym. (General) | typ. 0.3 dB (≤ 10 MHz/150 Ω) |
| Stripping length (Protective circuit) | 10 mm |
| Capacity (line-signalground) (General) | typ. 30 pF |
| Connection method (Protective circuit) | Push-in connection |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Pulse reset time (line-line) (General) | ≤ 15 ms |
| Response time tA(line-earth) (General) | ≤ 1 ns |
| Maximum continuous voltage UC (General) | 15 V DC |
| Pulse reset time (line-earth) (General) | ≤ 15 ms |
| Transmission speed (Ambient conditions) | 90 Mpbs |
| Direction of action (Ambient conditions) | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Impulse durability (line-line) (General) | C1 - 1 kV/500 A |
| Surge protection fault message (General) | Optical, multi-stage |
| Impulse durability (line-earth) (General) | C1 - 1 kV/500 A |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 70 °C |
| Operating effective current ICat UC (General) | ≤ 100 µA (per path) |
| Response time tA (line-signalground) (General) | ≤ 1 ns |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Voltage protection level Up(line-line) (General) | ≤ 90 V (C1 - 1 kV/500 A) |
| Voltage protection level Up(line-earth) (General) | ≤ 90 V (C1 - 1 kV/500 A) |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Total discharge current Itotal(8/20) µs (General) | 20 kA |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Voltage protection level Upstatic (line-line) (General) | ≤ 55 V (C1 - 1 kV/500 A) |
| Voltage protection level Upstatic (line-earth) (General) | ≤ 55 V (C1 - 1 kV/500 A) |
| Flammability rating according to UL 94 (Ambient conditions) | V0 |
| Nominal discharge current In(8/20) µs (line-line) (General) | 10 kA |
| Standards/specifications (Connection, equipotential bonding) | IEC 61643-21 2000 + A1:2008 + A2:2012 |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General) | typ. 60 MHz |
| Nominal discharge current In(8/20) µs (line-earth) (General) | 10 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) (General) | 2.5 kA |
| Standards for cearances and creepage distances (Ambient conditions) | IEC 60664-1 |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system (General) | typ. 60 MHz |
Technical specifications and performance data