Service time: Monday to Friday 9:00-18:00
PT-IQ-2X1+F-48DC-UT - PT-IQ-2X1+F-48DC-UT 2800790 PHOENIX CONTACT Surge protection device
In Stock Hot Product

PT-IQ-2X1+F-48DC-UT

PT-IQ-2X1+F-48DC-UT 2800790 PHOENIX CONTACT Surge protection device

$0.00USD
3135 in stock
Key Specifications
GTIN:4046356645133
Note:Made to Order (non-returnable)
Orderkey:2800790
Catalog page:Page 111 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356645133
NoteMade to Order (non-returnable)
Orderkey2800790
Catalog pagePage 111 (C-4-2017)
Packing unit1 pc
Country of originDE (Germany)
Custom tariff number85363010
Altitude (Dimensions)≤ 4000 m (amsl (above mean sea level))
Type (Ambient conditions)DIN rail module, two-section, divisible
(Additional descriptions)D1 - 2,5 kA
Color (Ambient conditions)jet black RAL 9005
Depth (Key Commercial Data)77.5 mm (incl. DIN rail 7.5 mm)
Width (Key Commercial Data)17.7 mm
(Remote indication contact)EN 61000-6-2 2005
Height (Key Commercial Data)91.1 mm
Degree of protection (Dimensions)IP20
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)DIN rail: 35 mm
Connection method (Connection data)DIN rail NS35
Weight per Piece (excluding packing)107.800 g
Housing material (Ambient conditions)PA 6.6
Stripping length (Protective circuit)8 mm
Connection method (Protective circuit)Screw connection
Horizontal pitch (Key Commercial Data)1 Div.
Tightening torque (Protective circuit)0.5 Nm
Rated current (Additional descriptions)300 mA
Direction of action (Ambient conditions)Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Ambient temperature (operation) (Dimensions)-40 °C ... 70 °C
Nominal voltage UN (Additional descriptions)48 V DC
Residual current IPE (Additional descriptions)≤ 1 µA
Resistance in series (Additional descriptions)1.2 Ω ±5 %
Capacity (line-earth) (Additional descriptions)typ. 1.5 nF
Conductor cross section AWG (Protective circuit)24 ... 12
IEC test classification (Additional descriptions)C1
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 85 °C
Max. required back-up fuse (Additional descriptions)315 mA (FF)
Standards/specifications (Remote indication contact)IEC 61643-21 2000 + A1:2008, modified
Conductor cross section flexible (Protective circuit)0.2 mm² ... 2.5 mm²
Input attenuation aE, asym. (Additional descriptions)typ. 0.3 dB (≤ 530 kHz / 150 Ω)
Response time tA(line-earth) (Additional descriptions)≤ 100 ns
Switching function (Connection, equipotential bonding)via DIN rail connector
Maximum continuous voltage UC (Additional descriptions)53 V DC
Pulse reset time (line-earth) (Additional descriptions)≤ 250 ms
Surge protection fault message (Additional descriptions)Optical, multi-stage
Impulse durability (line-earth) (Additional descriptions)C1 - 1 kV/500 A
Flammability rating according to UL 94 (Ambient conditions)V-0
Operating effective current ICat UC (Additional descriptions)≤ 6 µA (per path)
Pulse reset time (line-signalground) (Additional descriptions)≤ 1500 ms
Response time tA (line-signalground) (Additional descriptions)≤ 1 ns
Impulse durability (line-signalground) (Additional descriptions)C1 - 1 kV/500 A
Voltage protection level Up(line-earth) (Additional descriptions)≤ 750 V (C1 - 1 kV/500 A)
Total discharge current Itotal(8/20) µs (Additional descriptions)20 kA
Voltage protection level Up(line-signalground) (Additional descriptions)≤ 105 V (C1 - 1 kV/500 A)
Voltage protection level Upstatic (line-earth) (Additional descriptions)≤ 200 V (C2 - 10 kV / 5 kA)
Nominal discharge current In(8/20) µs (line-earth) (Additional descriptions)10 kA
Pulse discharge current Iimp(10/350) µs (line-earth) (Additional descriptions)2.5 kA
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system (Additional descriptions)typ. 1.9 MHz

Product Description

Surge protection, consisting of plug-in protection and base element, with multi-level status and diagnostic indication in module for two signal conductors with joint reference potential. Indir groundi
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top