Service time: Monday to Friday 9:00-18:00
PT 5-HF-24DC-ST - PT 5-HF-24DC-ST 2906002 PHOENIX CONTACT Surge protection device
In Stock Hot Product

PT 5-HF-24DC-ST

PT 5-HF-24DC-ST 2906002 PHOENIX CONTACT Surge protection device

$0.00USD
4364 in stock
Key Specifications
GTIN:4055626013398
Note:Made to Order (non-returnable)
Orderkey:2906002
(General):≤ 50 V (C3 - 25 A with PT 2X2-BE)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4055626013398
NoteMade to Order (non-returnable)
Orderkey2906002
(General)≤ 50 V (C3 - 25 A with PT 2X2-BE)
Catalog pagePage 160 (C-4-2017)
Packing unit1 pc
Country of originDE (Germany)
Custom tariff number85363010
Altitude (Dimensions)≤ 2000 m
Rated current (General)450 mA (45°C)
Type (Ambient conditions)Male
Color (Ambient conditions)black
Depth (Key Commercial Data)52 mm
Width (Key Commercial Data)17.7 mm
(Standards and Regulations)No hazardous substances above threshold values
Height (Key Commercial Data)45 mm
Nominal voltage UN (General)24 V DC
Capacity (line-line) (General)typ. 23 pF
Residual current IPE (General)≤ 5 µA (with PT 2X2-BE)
Resistance in series (General)2.2 Ω ±10 %
VDE requirement class (General)C1
Degree of protection (Dimensions)IP20
IEC test classification (General)C1
Screw thread (Protective circuit)M3
Stripping length (Connection data)8 mm
(Connection, equipotential bonding)IEC 61643-21/A2 2012
Input attenuation aE, sym. (General)typ. 0.3 dB (≤ 13 MHz/100 Ω)
Max. required back-up fuse (General)500 mA (T)
Weight per Piece (excluding packing)22.050 g
Housing material (Ambient conditions)PA 6.6
Response time tA(line-line) (General)≤ 500 ns
Stripping length (Protective circuit)8 mm
China RoHS (Standards and Regulations)Environmentally friendly use period: unlimited = EFUP-e
Connection method (Protective circuit)Screw connection (in connection with the base element)
Response time tA(line-earth) (General)≤ 500 ns
Tightening torque (Protective circuit)0.8 Nm
Maximum continuous voltage UC (General)28 V DC
Direction of action (Ambient conditions)Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Number of positions (Ambient conditions)5
Ambient temperature (operation) (Dimensions)-40 °C ... 85 °C
Operating effective current ICat UC (General)≤ 5 µA
Conductor cross section AWG (Protective circuit)24 ... 12
Voltage protection level Up(line-line) (General)≤ 150 V (C1 - 1 kV/500 A)
Voltage protection level Up(line-earth) (General)≤ 150 V (C1 - 1 kV/500 A)
Conductor cross section AWG max. (Connection data)12
Conductor cross section AWG min. (Connection data)24
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Pulse discharge current Iimp(10/350) µs (General)2.5 kA (with PT 2X2-BE)
Total discharge current Itotal(8/20) µs (General)20 kA
Conductor cross section solid max. (Connection data)4 mm²
Conductor cross section solid min. (Connection data)0.2 mm²
Conductor cross section flexible (Protective circuit)0.2 mm² ... 2.5 mm²
Conductor cross section flexible max. (Connection data)2.5 mm²
Conductor cross section flexible min. (Connection data)0.2 mm²
Voltage protection level Up(line-signalground) (General)≤ 150 V (C1 - 1 kV/500 A)
Flammability rating according to UL 94 (Ambient conditions)V-0
Nominal discharge current In(8/20) µs (line-line) (General)10 kA
Standards/specifications (Connection, equipotential bonding)EN 61643-21/A2 2013
Cut-off frequency fg (3 dB), sym. in 100 Ohm system (General)typ. 70 MHz
Nominal discharge current In(8/20) µs (line-earth) (General)10 kA (with PT 2X2+F-BE)
Nominal pulse current Ian (10/1000) µs (line-line) (General)25 A

Product Description

PT plug-in protection with AF protection circuit for 4 signal conductors. Rated voltage: 24 V DC
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide