| Parameter | Value |
|---|---|
| C2 | |
| Note | 2000 |
| Type | Male |
| Depth | 52 mm |
| Width | 17.7 mm |
| Height | 45 mm |
| Product type | Surge protection for MCR technology |
| Screw thread | M3 |
| Mounting type | on base element |
| Rated current | 300 mA (45 °C) |
| Product family | PLUGTRAB PT |
| Open side panel | No |
| Horizontal pitch | 1 Div. |
| Housing material | PA 6.6 |
| Pollution degree | 2 |
| Connection method | Screw connection (in connection with the base element) |
| Tightening torque | 0.8 Nm |
| Nominal voltage UN | 12 V AC |
| Dimensional drawing | |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Resistance per path | 4.7 Ω 10 % |
| Degree of protection | IP20 |
| Overvoltage category | III |
| Residual current IPE | ≤ 1 µA (with PT 4X1-BE) |
| Capacity (Core-Earth) | 2.5 nF |
| Complete module depth | 65.5 mm |
| Complete module width | 17.7 mm |
| Standards/regulations | VDE 0110-1 / IEC 60664-1 |
| VDE requirement class | C1 |
| Complete module height | 90 mm |
| IEC test classification | C1 |
| Standards/specifications | IEC 61643-21 |
| Max. required back-up fuse | 315 mA (T) |
| Conductor cross section AWG | 24 ... 12 |
| Input attenuation aE, asym. | 0.5 dB (≤ 700 kHz) |
| Response time tA(line-earth) | ≤ 1 ns |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Maximum continuous voltage UC | 18 V DC |
| Surge protection fault message | none |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Operating effective current ICat UC | ≤ 5 µA |
| Flammability rating according to UL 94 | V-0 |
| Voltage protection level Up(line-earth) | ≤ 70 V (C2 - 10 kV / 5 kA) |
| Residual voltage at In(conductor-ground) | ≤ 31 V |
| Pulse discharge current Iimp(10/350) µs | 2.5 A (per path) |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Nominal discharge current In(8/20) µs (line-ground) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 49 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 30 V |
| Cut-off frequency fg (3 dB), asym. (PE) in 50 Ω system | typ. 4 MHz |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 25 V |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Technical specifications and performance data
Installation and operation guide