| Parameter | Value |
|---|---|
| GTIN | 4017918182885 |
| Orderkey | 2839279 |
| (General) | II 1 D Ex iaD 20 IP6x T85 °C...135 °C |
| Catalog page | Page 132 (C-4-2017) |
| Packing unit | 10 pc |
| ATEX (General) | II 1 G Ex ia IIC T4...T6 |
| Country of origin | DE (Germany) |
| (Connection data) | IEC 60079-26 2006 |
| Custom tariff number | 85363010 |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Rated current (General) | 325 mA (≤40 °C) |
| (Conformity / approvals) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Type (Ambient conditions) | Base element, DIN rail mounting |
| Color (Ambient conditions) | sky blue RAL 5015 |
| Depth (Key Commercial Data) | 51.5 mm (incl. DIN rail 7.5 mm) |
| Width (Key Commercial Data) | 17.7 mm |
| (Standards and Regulations) | -40 °C ... 40 °C (T6) |
| Height (Key Commercial Data) | 90 mm |
| Nominal voltage UN (General) | 24 V DC |
| Resistance in series (General) | 2.2 Ω ±10 % |
| Degree of protection (Dimensions) | IP20 |
| Screw thread (Protective circuit) | M3 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| China RoHS (Conformity / approvals) | Environmentally Friendly Use Period = 50 |
| Max. required back-up fuse (General) | 315 mA (T) |
| Weight per Piece (excluding packing) | 62.430 g |
| Housing material (Ambient conditions) | PA 6.6 |
| Stripping length (Protective circuit) | 8 mm |
| Connection method (Protective circuit) | Screw connection |
| Horizontal pitch (Key Commercial Data) | 1 Div. |
| Tightening torque (Protective circuit) | 0.5 Nm |
| Maximum continuous voltage UC (General) | 30 V DC |
| Number of positions (Ambient conditions) | 4 |
| Surge protection fault message (General) | none |
| Standards/specifications (Connection data) | EN 61643-21 A2:2013 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| max. input power Pi (Standards and Regulations) | 3 W |
| Conductor cross section AWG (Protective circuit) | 24 ... 12 |
| Max. input current Ii (Standards and Regulations) | 325 mA (T4 / ≤ 80°C) |
| Max. input voltage Ui (Standards and Regulations) | 30 V DC |
| Conductor cross section solid (Protective circuit) | 0.2 mm² ... 4 mm² |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible (Protective circuit) | 0.2 mm² ... 2.5 mm² |
| Max. internal inductance Li (Standards and Regulations) | 1 µH |
| Maximum inner capacitance Ci (Standards and Regulations) | 1.3 nF |
| Ambient temperature (operation) (Standards and Regulations) | -40 °C ... 80 °C (T4) |
| Flammability rating according to UL 94 (Ambient conditions) | V-0 |
| Maximum inner time factor (Ri/Li) (Standards and Regulations) | ≤ 0.2 µs |
Technical specifications and performance data