Key Specifications
GTIN:4017918182663
Orderkey:2838254
(General):D1 - 2.5 kA
Catalog page:Page 99 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918182663
Orderkey2838254
(General)D1 - 2.5 kA
Catalog pagePage 99 (C-4-2017)
Packing unit10 pc
Country of originDE (Germany)
(Connection data)UL 497B
Custom tariff number85363010
(Ambient conditions)IEC 60664-1
Rated current (General)450 mA (45°C)
Type (Ambient conditions)Male
Color (Ambient conditions)black
Depth (Key Commercial Data)51.7 mm
Width (Key Commercial Data)17.5 mm
Height (Key Commercial Data)44.8 mm
Nominal voltage UN (General)12 V DC
Capacity (line-line) (General)3 nF
Residual current IPE (General)≤ 1 µA (with PT 2X2+F-BE)
Resistance in series (General)2.2 Ω
Degree of protection (Dimensions)IP20
IEC test classification (General)C1
Screw thread (Protective circuit)M3
Mounting type (Ambient conditions)on base element
Input attenuation aE, sym. (General)0.5 dB (≤ 600 kHz)
Weight per Piece (excluding packing)25.790 g
Housing material (Ambient conditions)PA 6.6
Input attenuation aE, asym. (General)
Response time tA(line-line) (General)≤ 1 ns
Stripping length (Protective circuit)8 mm
Connection method (Protective circuit)Screw connection (in connection with the base element)
Horizontal pitch (Key Commercial Data)1 Div.
Response time tA(line-earth) (General)≤ 100 ns
Tightening torque (Protective circuit)0.8 Nm
Maximum continuous voltage UC (General)13 V DC
Standards/regulations (Connection data)IEC 61643-21
Direction of action (Ambient conditions)Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Impulse durability (line-line) (General)C2 - 10 kV/5 kA
Surge protection fault message (General)none
Impulse durability (line-earth) (General)C2 - 10 kV/5 kA
Complete module depth (Key Commercial Data)65.5 mm
Complete module width (Key Commercial Data)17.7 mm
Residual voltage at In(line-line) (General)≤ 18 V
Ambient temperature (operation) (Dimensions)-40 °C ... 85 °C
Complete module height (Key Commercial Data)90 mm
Operating effective current ICat UC (General)≤ 5 µA
Conductor cross section AWG (Protective circuit)24 ... 12
Conductor cross section solid (Protective circuit)0.2 mm² ... 4 mm²
Pulse discharge current Iimp(10/350) µs (General)2.5 kA (per path)
Total discharge current Itotal(8/20) µs (General)20 kA
Residual voltage at In(line-signalground) (General)≤ 450 V
Conductor cross section flexible (Protective circuit)0.2 mm² ... 2.5 mm²
Flammability rating according to UL 94 (Ambient conditions)V-0
Cut-off frequency fg (3 dB), sym. in 50 Ohm system (General)typ. 3 MHz
Nominal discharge current In(8/20) µs (line-line) (General)10 kA
Nominal discharge current In(8/20) µs (line-earth) (General)10 kA
Output voltage limitation (10/700) µs (line-earth) (General)≤ 450 V
Residual voltage with Ian (10/1000) µs (line-line) (General)≤ 23 V
Output voltage limitation at 1 kV/µs (line-line) spike (General)≤ 20 V
Output voltage limitation at 1 kV/µs (line-earth) spike (General)≤ 450 V
Output voltage limitation at 1 kV/µs (line-line) static (General)≤ 18 V
Max. discharge current Imax(8/20) µs maximum (line-line) (General)10 kA
Standards for cearances and creepage distances (Ambient conditions)VDE 0110-1
Max. discharge current Imax(8/20) µs maximum (line-earth) (General)10 kA
Output voltage limitation (10/700) µs (line-signalground) (General)≤ 18 V
Arrester can be tested with CHECKMASTER from software version: (Ambient conditions)From SW rev. 1.00

Product Description

PT plug-in protection with circ. of Protec. for two circ. 2 cond. Floating. Nominal voltage: 12 V DC. Suitable for HART.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents